Standard
RLL
Instructions
5--69
Standard RLL Instructions
Bit Operation Instructions
DL105 PLC User Manual, 3rd Edition
ENCO
The Encode instruction encodes the bit
position in the accumulator having a value
of 1, and returns the appropriate binary
representation. If the most significant bit is
set to 1 (Bit 31), the Encode instruction
would place the value HEX 1F (decimal
31) in the accumulator. If the value to be
encoded is 0000 or 0001, the instruction
will place a zero in the accumulator. If the
value to be encoded has more than one bit
position set to a “1”, the least significant “1”
will be encoded and SP53 will be set on.
Discrete Bit Flags
Description
SP53
On when the value of the operand is larger than the accumulator can work
with.
NOTE:
The status flags are only valid until another instruction that uses the same
flags is executed.
In the following example, when X1 is on, The value in V2000 is loaded into the
accumulator using the Load instruction. The bit position set to a “1” in the
accumulator is encoded to the corresponding 5 bit binary value using the Encode
instruction. The value in the lower 16 bits of the accumulator is copied to V2010
using the Out instruction.
Handheld Programmer Keystrokes
Direct
SOFT
LD
V2000
X1
Load the value in V2000 into
the lower 16 bits of the
accumulator
ENCO
Encode the bit position set
to “1” in the accumulator to a
5 bit binary value
0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Acc.
0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Acc.
V2000
1 0 0 0
Bit postion 12 is
converted
to binary
Copy the value in the lower 16 bits
of the accumulator to V2010
OUT
V2010
V2010
0 0 0 C
Binary value
for 12.
STR
$
1
B
ENT
SHFT
OUT
GX
SHFT
AND
V
2
C
0
A
1
B
0
A
ENT
4
E
TMR
N
2
C
INST#
O
ENT
SHFT
ANDST
L
3
D
2
C
0
A
0
A
0
A
ENT
Encode
(ENCO)
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...