ECOM100 IP Setup (ECIPSUP) (IB-717)
ECOM100 IP Setup will configure the three TCP/IP parameters in the ECOM100: IP
Address, Subnet Mask, and Gateway Address, on a leading edge transition to the IBox. The
ECOM100 is specified by the ECOM100#, which corresponds to a specific unique ECOM100
Configuration (ECOM100) IBox at the top of your program.
This setup data is stored in Flash-ROM in the ECOM100 and will disable the ECOM100
module for at least a half second until it writes the Flash-ROM. Therefore, it is HIGHLY
RECOMMENDED that you only execute this IBox ONCE on first scan. Since it requires a
LEADING edge to execute, use a NORMALLY CLOSED SP0 (NOT First Scan) to drive the
power flow to the IBox.
In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the
ECOM100 circuit board.
ECIPSUP Parameters
• ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified
slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this
logical number
• Workspace: specifies a V-memory location that will be used by the instruction
• Success: specifies a bit that will turn on once the request is completed successfully
• Error: specifies a bit that will turn on if the instruction is not successfully completed
• Error Code: specifies the location where the Error Code will be written
• IP Address: specifies the module’s IP Address
• Subnet Mask: specifies the Subnet Mask for the module to use
• Gateway Address: specifies the Gateway Address for the module to use
DS
Used
HPP
N/A
Parameter
DL06 Range
ECOM100#
K
K0-255
Workspace
V
See DL06 V-memory map - Data Words
Success
X,Y,C,GX,GY,B
See DL06 V-memory map
Error
X,Y,C,GX,GY,B
See DL06 V-memory map
Error Code
V
See DL06 V-memory map - Data Words
IP Address
IP Address
0.0.0.1. to 255.255.255.254
Subnet Mask Address
IP Address Mask
0.0.0.1. to 255.255.255.254
Gateway Address
IP Address
0.0.0.1. to 255.255.255.254
The Workspace parameter is an internal, private
register used by this IBox and MUST BE UNIQUE
in this one instruction and MUST NOT be used
anywhere else in your program.
Either the Success or Error bit parameter will turn on
once the command is complete. If there is an error,
the Error Code parameter will report an ECOM100
error code (less than 100), or a PLC logic error
(greater than 1000).