DL06 Micro PLC User Manual, 3rd Edition, Rev. E
Chapter 2: Installation, Wiring, and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
2-35
D0-06DA General Specifications
External Power Requirements
100–240 VAC/ 50–60 Hz, 40VA maximum
Communication Port 1 9600 baud (Fixed), 8 data
bits, 1 stop bit, odd parity
K–Sequence (Slave), DirectNET (Slave),
MODBUS (Slave)
Communication Port 2 9600 baud (default), 8 data
bits, 1 stop bit, odd parity
K–Sequence (Slave), DirectNET (Master/Slave),
MODBUS (Master/Slave), Non-sequence/print, ASCII in/out
Programming cable type
D2–DSCBL
Operating Temperature
32 to 131°F (0 to 55°C)
Storage Temperature
–4 to 158°F (–20 to 70°C)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3–304
Terminal Type
Removable
Wire Gauge
One 16 AWG or two 18 AWG, 24 AWG minimum
DC Input Specifications
Parameter
High–Speed Inputs, X0 – X3
Standard DC Inputs X4 – X23
Input Voltage Range
10.8–26.4 VDC
10.8–26.4 VDC
Operating Voltage Range
12–24 VDC
12–24 VDC
Maximum Voltage
30VDC (7kHz maximum frequency)
30VDC
Minimum Pulse Width
70µs
N/A
ON Voltage Level
> 10VDC
> 10VDC
OFF Voltage Level
< 2.0 VDC
< 2.0 VDC
Input Impedance
1.8 k
q
@ 12–24 VDC
2.8 k
q
@ 12–24 VDC
Minimum ON Current
>5mA
>4mA
Maximum OFF Current
< 0.5 mA
<0.5 mA
OFF to ON Response
<70µs
2–8 ms, 4ms typical
ON to OFF Response
<70µs
2–8 ms, 4ms typical
Status Indicators
Logic side
Logic side
Commons
4 channels / common x 5 bank (isolated)
AC Output Specifications
Output Voltage Range (Min. - Max.)
15–264 VAC, 47–63 Hz
Operating Voltage
17–240 VAC, 47–63 Hz
On Voltage Drop
1.5 VAC @> 50mA, 4VAC @< 50mA
Max Current
0.5 A / point, 1.5 A / common
Max leakage current
< 4mA @ 264VAC, 60Hz
Max inrush current
10A for 10ms
Minimum Load
10mA
OFF to ON Response
1ms
ON to OFF Response
1 ms +1/2 cycle
Status Indicators
Logic Side
Commons
4 channels / common x 4 banks (isolated)
Fuses
None (external recommended)