DL06 Micro PLC User Manual, 3rd Edition, Rev. E
5-92
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 will be loaded into the accumulator
using the Load instruction. The value in V2006 is multiplied by the value in the accumulator.
The value in the accumulator is copied to V2010 and V2011 using the Out Double instruction.
MUL
A aaa
Direct SOFT32
Handheld Programmer Keystrokes
LD
V2000
X1
Load the value in V2000 into
the lower 16 bits of the
accumulator
MUL
V2006
The value in V2006 is
multiplied by the value in the
accumulator
OUTD
V2010
Copy the value in the
accumulator to V2010 and
V2011
0 0 0 2 5 0 0 0
0
X
0 0 0 0
1 0 0 0
V2010
1
V2000
0
0 0 0 2 5 0 0 0
2
5
The unused accumulator
bits are set to zero
Acc.
STR
$
SHFT
ANDST
L
3
D
SHFT
ORST
M
ISG
U
ANDST
L
OUT
GX
SHFT
3
D
1
B
ENT
2
C
0
A
0
A
0
A
ENT
2
C
0
A
0
A
ENT
6
G
2
C
0
A
1
B
0
A
ENT
0
V2011
(Accumulator)
(V2006)
Discrete Bit Flags
Description
SP63
On when the result of the instruction causes the value in the accumulator to be zero.
SP70
On anytime the value in the accumulator is negative.
SP75
On when a BCD instruction is executed and a NON–BCD number was encountered.
Operand Data Type
DL06 Range
A
aaa
V-memory
V
See memory map
Pointer
P
See memory map
Constant
K
0–9999
DS
Used
HPP Used
Direct
SOFT
Multiply (MUL)
Multiply is a 16-bit instruction that multiplies the BCD value
(Aaaa), which is either a V-memory location or a 4–digit
(max.) constant, by the BCD value in the lower 16 bits of the
accumulator The result can be up to 8 digits and resides in the
accumulator.