DL06 Micro PLC User Manual, 3rd Edition, Rev. E
5-121
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
In the following example, when X1 is on, the value in V2000 and V2001 will be loaded into
the accumulator using the Load Double instruction. The bit pattern in the accumulator is
shifted 2 bits to the left using the Shift Left instruction. The value in the accumulator is copied
to V2010 and V2011 using the Out Double instruction.
NOTE: Status flags are valid only until another instruction uses the same flag.
2
C
ENT
Handheld Programmer Keystrokes
Direct SOFT32
LDD
V2000
X1
Load the value in V2000 and
V2001 into the accumulator
SHFL
K2
The bit pattern in the
accumulator is shifted 2 bit
positions to the left
OUTD
V2010
Copy the value in the
accumulator to V2010 and
V2011
0 0 1 1 0 0 0 1 0 0 0 0 0 0 0 1
V2010
1 1 0 0 0 1 0 0 0 0 0 0 0 1 0 0
0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
C 4 0 4
. . . .
1 0 0 1 1 1 0 0 0 0 0 1 0 1 0 0
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
0 1 1 0 0 1 1 1 0 0 0 0 0 1 0 1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Acc.
Acc.
V2011
9 C 1 4
6 7 0 5 3 3 1 0
3
1
0
1
Shifted out of the
accumulator
V2000
V2001
STR
$
SHFT
ANDST
L
3
D
3
D
SHFT
RST
S
7
H
5
F
ANDST
L
OUT
GX
SHFT
3
D
1
B
ENT
2
C
0
A
0
A
0
A
ENT
2
C
0
A
1
B
0
A
ENT
SHFT
Operand Data Type
DL06 Range
A
aaa
V-memory
V
See memory map
Constant
K
1-32
Discrete Bit Flags
Description
SP63
On when the result of the instruction causes the value in the accumulator to be zero.
SP70
On anytime the value in the accumulator is negative.
SHFL
A aaa
DS
Used
HPP Used
Direct
SOFT
Shift Left (SHFL)
Shift Left is a 32-bit instruction that shifts the bits in the
accumulator a specified number (Aaaa) of places to the left.
The vacant positions are filled with zeros and the bits shifted