DL06 Micro PLC User Manual, 3rd Edition, Rev. E
Chapter 2: Installation, Wiring, and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
2-39
D0-06DD2 General Specifications
External Power Requirements
100–240 VAC/50–60 Hz, 40VA maximum
Communication Port 1 9600 baud (Fixed),
8 data bits, 1 stop bit, odd parity
K–Sequence (Slave), DirectNET (Slave),
MODBUS (Slave)
Communication Port 2 9600 baud (default),
8 data bits, 1 stop bit, odd parity
K–Sequence (Slave), DirectNET (Master/Slave),
MODBUS (Master/Slave), Non-sequence / print, ASCII in/out
Programming cable type
D2–DSCBL
Operating Temperature
32 to 131°F (0 to 55°C)
Storage Temperature
–4 to 158°F (–20 to 70°C)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3–304
Terminal Type
Removable
Wire Gauge
One 16 AWG or two 18 AWG, 24 AWG minimum
DC Input Specifications
Parameter
High–Speed Inputs, X0 – X3
Standard DC Inputs X4 – X23
Min. - Max. Voltage Range
10.8–26.4 VDC
10.8–26.4 VDC
Operating Voltage Range
12–24 VDC
12–24 VDC
Peak Voltage
30 VDC (7 kHz maximum frequency)
30VDC
Minimum Pulse Width
70 µs
N/A
ON Voltage Level
> 10.0 VDC
> 10.0 VDC
OFF Voltage Level
< 2.0 VDC
< 2.0 VDC
Max. Input Current
6mA @ 12VDC, 13mA @ 24VDC
4mA @ 12VDC, 8.5 mA @ 24VDC
Input Impedance
1.8
q
k @ 12–24 VDC
2.8
q
k @ 12–24 VDC
Minimum ON Current
>5mA
>4mA
Maximum OFF Current
< 0.5 mA
<0.5 mA
OFF to ON Response
<70µs
2–8 ms, 4ms typical
ON to OFF Response
<70µs
2–8 ms, 4ms typical
Status Indicators
Logic side
Logic side
Commons
4 channels/common x 5 banks (isolated)
DC Output Specifications
Parameter
Pulse Outputs Y0 – Y1
Standard Outputs Y2 – Y17
Min. - Max. Voltage Range
10.8–26.4 VDC
10.8–26.4 VDC
Operating Voltage
12–24 VDC
12–24 VDC
Peak Voltage
< 50VDC (10kHz max. frequency)
< 50VDC
On Voltage Drop
0.5 VDC @ 1A
1.2 VDC @ 1A
Max Current (resistive)
0.5 A / pt., 1A / pt. as standard pt.
1.0 A / point
Max leakage current
15µA @ 30VDC
15µA @ 30VDC
Max inrush current
2A for 100ms
2A for 100ms
External DC power required
12–24 VDC
12 -24 VDC
OFF to ON Response
< 10µs
< 10µs
ON to OFF Response
< 20µs
< 0.5 µs
Status Indicators
Logic Side
Logic Side
Commons
4 channels / common x 4 banks (non-isolated)
Fuses
None (external recommended)