background image

Do-more H2 Series PLC Hardware User Manual, 1st Edition, Rev. F - H2-DM-M

5–11

Chapter 5: Specifications - Discrete I/O Modules

1
2
3
4
5
6
7
8
9

10
11
12
13
14

A

B

C

D

D2-16NA, AC Input

D2-16NA  AC Input

Inputs per Module

16

Commons per Module

2 (isolated)

Input Voltage Range

80–132 VAC

Peak Voltage

132VAC

ON Voltage Level

70VAC minimum

OFF Voltage Level

20VAC maximum

AC Frequency

47–63 Hz

Input Impedance

12k

q

 @ 60Hz

Input Current

11mA @ 100VAC, 50Hz

13mA @ 100VAC, 60Hz
15mA @ 132VAC, 60Hz

Minimum ON Current

5mA

Maximum OFF Current 

2mA

Base Power Required 5VDC

100mA

OFF to ON Response

5 to 30 ms

ON to OFF Response

10 to 50 ms

Terminal Type (included)

Removable; D2-16IOCON

Status Indicator

Logic side

Weight

2.4 oz. (68g)

ZIPLink Module

ZL-RTB20 (Feedthrough)

ZIPLink Cable

ZL-D2-CBL19 (0.5 m)

ZL-D2-CBL19-1 (1.0 m)

ZL-D2-CBL19-2 (2.0 m)

ZL-D2-CBL19-1P (1.0 m Pigtail)

ZL-D2-CBL19-2P (2.0 m Pigtail)

0

10

20

30

40

50 55

Ambient Temperature (°C/°F )

32

50

68

86

104

122131

C

°

F

°

0

4

8

12

16

Points

Derating Chart

0

1

2

3

5

6

7

NC

0

1

2

3

CB

4

5

6

7

CA

4

110 VAC

110 VAC

Optical

Isolator

INPUT

110 VAC

V+

To LE D

Internal module circuitry

COM

80-132VAC

10-20mA

50/60Hz

D2-16NA

IN

110

VAC

0

1

2

3

4

5

6

7

CA

CB

NC

A

B

Содержание Do-more H2 PLC Series

Страница 1: ...er Manual Manual Number H2 DM M H2 DM1E D2 08ND3 IN 12 24 VDC 0 1 2 3 4 5 6 7 D2 08ND3 IN 12 24 VDC 0 1 2 3 4 5 6 7 OUT A B F2 16TD1P 12 24 VDC 10 2 26 4 VDC 0 25A CLASS2 A 0 1 2 3 24V 0 1 2 3 B 0V 4...

Страница 2: ...Notes...

Страница 3: ...in hazardous environments requiring fail safe performance such as in the operation of nuclear facilities aircraft navigation or communication systems air traffic control direct life support machines o...

Страница 4: ...vida o sistemas de armamentos en las cuales la falla del producto puede resultar directamente en muerte heridas personales o da os f sicos o ambientales severos Actividades de Alto Riesgo Automationdi...

Страница 5: ...n cessitant une s curit absolue par exemple l exploitation d installations nucl aires les syst mes de navigation a rienne ou de communication le contr le de la circulation a rienne les quipements de s...

Страница 6: ...Notes...

Страница 7: ...ory Issue Date Description of Changes 1st Edition 9 12 Original Revision A 9 12 Minor corrections made throughout manual Revision B 02 13 Added H2 ERM100 module data Minor corrections made throughout...

Страница 8: ...Notes...

Страница 9: ...ore Designer Software System Requirements 1 5 Step 1 Install Do more Designer Software 1 6 Step 2 Launch Do more Designer Software 1 9 Step 3 Install Hardware 1 11 Step 4 Apply Power to the Do more PL...

Страница 10: ...cations 3 4 Port 1 Specifications USB 3 4 Port 2 Specifications Serial 3 4 USB Type B Slave Input Specifications 3 4 Port 3 Specifications Ethernet 3 5 Ethernet Specifications 3 5 Ethernet Expansion I...

Страница 11: ...put 5 10 D2 16NA AC Input 5 11 D2 04TD1 DC Output 5 12 D2 08TD1 DC Output 5 13 D2 08TD2 DC Output 5 14 D2 16TD1 2 DC Output 5 15 D2 16TD2 2 DC Output 5 16 F2 16TD1P DC Output With Fault Protection 5 1...

Страница 12: ...dule Jumpers 6 11 F2 04AD 2 L Addressing 6 12 F2 08AD 1 Analog Input 6 13 Setting the Module Jumpers 6 14 F2 08AD 1 Addressing 6 15 F2 08AD 2 Analog Input 6 16 Setting the Module Jumpers 6 17 F2 08AD...

Страница 13: ...Version 1 1 or Newer 6 59 Input Resolution Selection WYn 4 6 60 Input and Output Range Selection WYn 5 6 61 Input Track and Hold Selection WYn 6 6 62 Chapter 7 Specifications Specialty Modules Special...

Страница 14: ...100 LED Indicators 7 23 H2 EBC100 Overview 7 23 H2 EBC100 Specifications 7 23 H2 EBC100 LED Indicators 7 24 H2 ERM 100 H2 EBC100 Network Identifiers 7 24 H2 ERM 100 H2 EBC100 Network Layouts 7 27 H2...

Страница 15: ...I O Modules Position and Wiring 8 13 Slot Numbering 8 13 Module Placement Restrictions 8 13 Wiring the Different Module Connectors 8 14 I O Wiring Checklist 8 15 ZIPLink Wiring System 8 16 I O Wiring...

Страница 16: ...C Hardware User Manual 1st Edition Rev F H2 DM M viii Appendix A Do more Product Weight Table Do more Product Weight Table A 2 Appendix B European Union Directives CE European Union EU Directives B 2...

Страница 17: ...1 5 Do more Designer Software System Requirements 1 5 Step 1 Install Do more Designer Software 1 6 Step 2 Launch Do more Designer Software 1 9 Step 3 Install Hardware 1 11 Step 4 Apply Power to the D...

Страница 18: ...applying power to the PLC establishing a communications link and creating saving and writing a project to the CPU Once these steps are completed your Do more PLC will be running a ladder logic project...

Страница 19: ...n in the left hand margin the paragraph to its immediate right will be a warning This information could prevent injury loss of property or even death in extreme cases Any warning in this manual should...

Страница 20: ...n also use an Ethernet or Serial D2 DSCBL cable for programming but we recommend using a USB cable just plug it in and it works USB A to USB B Programming Cable PC Running Windows XP Vista Windows 7 W...

Страница 21: ...put and output signal ranges including bipolar Several specialty modules are also available Do more Designer Software System Requirements The Do more Designer Windows based programming software works...

Страница 22: ...lready installed this screen will detail the version number of the software being replaced and the one being installed click Next to continue An alert window will appear requesting that all anti virus...

Страница 23: ...to install whereas Complete installation installs all of the program features available The Complete installation is selected by default and is recommended for first time users Select the installation...

Страница 24: ...tware on your PC s desktop Click Yes or No to continue with the installation The software will now install the needed files and folders with the Setup Status window detailing the status of the install...

Страница 25: ...PC s Start menu or All Programs menu If the software link is not embedded in the Start menu use the path Start All Programs Do more Designer x x Do more Designer x x to launch the software The Do mor...

Страница 26: ...on to store the project or use the default location Click OK after your selections have been made to continue The Main programming window and Instruction Palette shown below will open The Instruction...

Страница 27: ...ps to firmly secure the module to the base WARNING Minimize the risk of electrical shock personal injury or equipment damage Always disconnect the system power before installing or removing any system...

Страница 28: ...WG is the recommended size Do not over tighten the connector screws the recommended torque value is 7 81 lb in 0 882 N m NOTE You can connect either a 115VAC or 220VAC supply to the AC terminals Once...

Страница 29: ...ications link To open the Link Wizard select the New Link button in the Links section of the Main Page s Launchpad as shown below The Link Wizard will first ask you to choose which communications port...

Страница 30: ...configure each link by selecting the Link Editor button from the lower left corner of the Link Wizard The Configure Link dialog will open as seen below allowing you to select PLC types port parameters...

Страница 31: ...isable enable or delete links Choose the appropriate link select OK and the software will connect to the Do more PLC If the mode selector switch on the CPU module is not in the Term position when conn...

Страница 32: ...isplays may show incorrect information If the memory configuration in the disk based project contains elements that are incompatible with the memory configuration currently in the Do more PLC the mess...

Страница 33: ...mparison are red which notes items that exist only in the project on the PC and not in the PLC and black which highlights items that are identical in both projects There are also numerous checkbox and...

Страница 34: ...ive Notice the status bar indications which show PLC type memory usage communication status PLC errors PLC mode etc Hovering your mouse over the status bar will highlight the items that are selectable...

Страница 35: ...onfiguration tab in the Project Browser or by clicking the XY Configure icon in the Project Toolbar On the left side of the System Configuration window is an index of topics titled Configuration Entri...

Страница 36: ...led and they must match for the PLC to work properly NOTE If the manually configured I O modules do not match the installed I O modules the PLC will not go into Run Mode After you have set the configu...

Страница 37: ...configuration will allow you to place that module in an Optional state This will allow the PLC to function properly without any hardware mismatch errors As previously mentioned the Do more PLC will n...

Страница 38: ...s index This option will display the assigned addresses for the configured modules as seen below These X Y WX and WY addresses are automatically assigned by Do more Designer You have the option to man...

Страница 39: ...blue Now you are ready to begin entering the example ladder logic below Rung 1 Place the box cursor in the NOP position on Rung 1 If the Instruction Palette is not open then click Instructions from t...

Страница 40: ...l be T1 Done This feature works for all structures including timers counters PID loops and strings Many system data types such as Main and FirstScan as well as user created devices like ECOM CTRIO or...

Страница 41: ...otice the shortcuts that are available for wire drawing The wire that should now appear in your ladder could have also been drawn using the shortcut Ctrl Down Arrow NOTE There are also Delete Wire opt...

Страница 42: ...Lastly you will need to add an Out coil to the end of Rung 2 Place the cursor at the end of the rung and either select Out from the Ladder Palette Bar or just type OUT and select the Out instruction f...

Страница 43: ...gin signifies logic that has not been accepted So once you have verified your logic click the Accept button in the Project Toolbar or the Ladder Palette Bar to accept the changes You should now see bl...

Страница 44: ...utton is not active then you must first connect to the PLC to activate the online portion of the Project Toolbar see the Establish Communication section of this chapter If you have altered the System...

Страница 45: ...er elements entered into the Data View window you now need to activate their status To do so click the All Status icon on the Project Toolbar or select Debug All Status On The All Status On option wil...

Страница 46: ...1_Start s current value is OFF Click the ON button under the Edits column and the Write Current Edit and the Writes All Edits buttons will appear at the top of the window These buttons will write indi...

Страница 47: ...free to experiment with a program of your own and don t forget that the software Help file is an essential tool to use when programming your controller Accessing the Help File TheDo more Designersoftw...

Страница 48: ...Do more H2 Series PLC Hardware User Manual 1st Edition Rev F H2 DM M 1 32 Chapter 1 Getting Started 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D Notes...

Страница 49: ...Do more H2 Series PLC Overview 2 2 2 Chapter Chapter Chapter In This Chapter Do more H2 Series PLC Overview 2 2 Do more DL205 System Compatibility 2 3 Communications 2 4...

Страница 50: ...nstruction Set for ladder programs The new Do more Designer software with advanced programming and monitoring features will be used to create your new programs NOTE Because the Do more PLC supports a...

Страница 51: ...F2 04RTD D2 04BDC1 1 F2 04THM D2 06BDC1 1 F2 02DA 1 L D2 09BDC1 1 F2 02DA 2 L D2 06BDC2 1 F2 02DAS 1 D2 09BDC2 1 F2 02DAS 2 Discrete I O Modules D2 08ND3 F2 08DA 1 D2 16ND3 2 F2 08DA 2 D2 32ND3 F2 4AD...

Страница 52: ...Yes Yes Ethernet IP Yes Modbus RTU Client Master Yes Yes Modbus RTU Server Slave Yes Yes Modbus TCP Client Master Yes Yes Modbus TCP Server Slave Yes Yes DirectLOGIC RX WX Client Master Yes Yes Yes D...

Страница 53: ...nications Ports Specifications 3 4 Port 1 Specifications USB 3 4 Port 2 Specifications Serial 3 4 USB Type B Slave Input Specifications 3 4 Port 3 Specifications Ethernet 3 5 Ethernet Specifications 3...

Страница 54: ...RS 232 USB RS 232 Ethernet 10 100 Base T Program Memory Flash ROM Total I O points available X Y each configurable up to 65536 2048 default WX WY analog in out each configurable up to 65536 256 defaul...

Страница 55: ...it default 512 X 512 Y 512 C 2048 V Immediate I O No Interrupt input hardware timed No Subroutines Program and Task code blocks up to memory limit Drum Timers Yes up to memory limit Table Instructions...

Страница 56: ...ype B Slave Input Specifications Description Standard USB 2 0 Slave input for programming and online monitoring only with built in surge protection Not compatible with older full speed USB devices Cab...

Страница 57: ...thernet IP Ethernet Expansion I O Master NOTE The above diagram illustrates the standard wire positions in the RJ45 connector It is recommended that all 10 100 Base T cables be Category 5 UTP cables E...

Страница 58: ...I O GS EDRV100 GS Drives The Ethernet Expansion I O network uses Category 5 UTP cables for cable runs up to 100 meters 328ft with extended distances achieved through Ethernet switches WARNING It is hi...

Страница 59: ...down menu select System Configuration Then from the System Configuration window select the CPU Configuration option under the Configuration Entries column Finally left click the Enable Ethernet I O M...

Страница 60: ...ons The mode switch on the Do more CPU allows the user to externally select the different modes of operation There are three modes available RUN TERM and STOP Mode Switch Functions Mode Switch Positio...

Страница 61: ...first powered up Changing the settings of the DIP switches requires that the base containing the controller be powered down and the controller removed from the base The DIP switches can then be chang...

Страница 62: ...ot loader sequence that is they should be blinking in sequence from top to bottom then back to the top alternating between red and green Move the controller mode switch to RUN to the left Move the con...

Страница 63: ...tween red and green Move the controller mode switch to RUN to the left Move the controller mode switch to TERM to the center Move the controller mode switch to RUN to the left Move the controller mode...

Страница 64: ...Disk before performing this operation Power down the system containing the controller Remove the controller from the base Remove the battery from it s holder that is located on the back of the control...

Страница 65: ...pter Chapter Chapter In This Chapter Base Unit Overview 4 2 Choosing a Base Type 4 2 AC Powered Base Units 4 3 24VDC Powered Base Units 4 4 125VDC Powered Base Units 4 5 Power Budget 4 6 Power Budget...

Страница 66: ...more PLC offers 10 base configurations four chassis sizes with different power supply options The following diagram shows an example of a 6 slot base Your choice of base depends on three things Numbe...

Страница 67: ...n 100 240 VAC Powered Bases Input Voltage Range 100 240 VAC 10 15 50 60 Hz Maximum Inrush Current 30A Maximum Power 80VA Voltage Withstand dielectric 1 minute 1500VAC between primary secondary and fie...

Страница 68: ...28 8VDC D2 09BDC 1 12 24VDC 10 2 28 8VDC Specification 12 24 VDC Powered Bases Input Voltage Range 10 2 28 8 VDC with less than 10 ripple Maximum Inrush Current 10A Maximum Power 25W Voltage Withstan...

Страница 69: ...Voltage Range 104 240 VDC 10 15 Maximum Inrush Current 20A Maximum Power 30W Voltage Withstand dielectric 1 minute 1500VAC between primary secondary and field ground Insulation Resistance 10M at 500VD...

Страница 70: ...d and used by each device columns 3 and 4 Devices which fall into the Other category Row D are devices such as the C more Micro interface which also have power requirements but do not directly plug in...

Страница 71: ...er Supplied Device 5V mA 24V Auxiliary Device 5V mA 24V Auxiliary Bases Bases D2 03B 1 2600 300 D2 04BDC1 1 2600 None D2 04B 1 2600 300 D2 06BDC1 1 2600 None D2 06B 1 2600 300 D2 09BDC1 1 2600 None D2...

Страница 72: ...Do more H2 Series PLC Hardware User Manual 1st Edition Rev F H2 DM M 4 8 Chapter 4 Specifications Base Units 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D Notes...

Страница 73: ...D2 32ND3 DC Input 5 7 D2 32ND3 2 DC Input 5 8 D2 08NA 1 AC Input 5 9 D2 08NA 2 AC Input 5 10 D2 16NA AC Input 5 11 D2 04TD1 DC Output 5 12 D2 08TD1 DC Output 5 13 D2 08TD2 DC Output 5 14 D2 16TD1 2 DC...

Страница 74: ...Rev E H2 DM M 5 2 Table of Contents 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D D2 04TRS Relay Output 5 26 D2 08TR Relay Output 5 27 F2 08TR Relay Output 5 28 F2 08TRS Relay Output 5 29 D2 12TR Relay Ou...

Страница 75: ...signifies an Input I O module a red bar signifies an Output I O module and a White bar signifies a combination Input Output module Module Type Blue Input Discrete Input Modules Part Number Number of...

Страница 76: ...4 Isolated Relay Output 5 25 D2 08TR 8 Relay Output 5 26 F2 08TR 8 Relay Output 5 27 F2 08TRS 8 Isolated Relay Output 5 28 D2 12TR 12 Relay Output 5 29 Discrete Output Modules 0 1 2 3 C C C C L L L L...

Страница 77: ...FF Current 1 5 mA Base Power Required 5VDC 50mA OFF to ON Response 1 to 8 ms ON to OFF Response 1 to 8 ms Terminal Type included Removable D2 8IOCON Status Indicator Logic side Weight 2 3 oz 65g ZIPLi...

Страница 78: ...e Power Required 5VDC 100mA OFF to ON Response 3 to 9 ms ON to OFF Response 3 to 9 ms Terminal Type included Removable D2 16IOCON Status Indicator Logic side Weight 2 3 oz 65g ZIPLink Module ZL RTB20...

Страница 79: ...dicator Module Activity LED Weight 2 1 oz 60g ZIPLink Module ZL RTB40 Feedthrough ZL LTB32 24 Sensor Input ZIPLink Cable ZL D24 CBL40 0 5 m ZL D24 CBL40 1 1 0 m ZL D24 CBL40 2 2 0 m ZL D24 CBL40 1P 1...

Страница 80: ...Power Required 5VDC 25mA OFF to ON Response 3 to 9 ms ON to OFF Response 3 to 9 ms Terminal Type not included Removable 40 pin connector1 Status Indicator Module activity LED Weight 2 1 oz 60g ZIPLink...

Страница 81: ...OFF Current 2mA Base Power Required 5VDC 50mA OFF to ON Response 5 to 30 ms ON to OFF Response 10 to 50 ms Terminal Type included Removable D2 8IOCON Status Indicator Logic side Weight 2 5 oz 70g ZIP...

Страница 82: ...ON Current 10mA Maximum OFF Current 2mA Base Power Required 5VDC 100mA OFF to ON Response 5 to 30 ms ON to OFF Response 10 to 50 ms Terminal Type included Removable D2 8IOCON Status Indicator Logic s...

Страница 83: ...rent 5mA Maximum OFF Current 2mA Base Power Required 5VDC 100mA OFF to ON Response 5 to 30 ms ON to OFF Response 10 to 50 ms Terminal Type included Removable D2 16IOCON Status Indicator Logic side Wei...

Страница 84: ...t and 2 Amps per common when using the ZIPLink wiring system At 40mS duration loads of 3 0 A or greater cannot be used At 100mS duration loads of 2 0 A or greater cannot be used Find the load current...

Страница 85: ...0ms Base Power Required 5VDC 100mA OFF to ON Response 1ms ON to OFF Response 1ms Terminal Type included Removable D2 8IOCON Status Indicator Logic side Weight 2 3 oz 65g Fuses 1 per common 5A fast blo...

Страница 86: ...d Current N A Max Load Current 0 3 A per point 2 4 A per common Max Leakage Current 1 0 mA 40VDC Max Inrush Current 1A for 10ms Base Power Required 5VDC 100mA OFF to ON Response 1ms ON to OFF Response...

Страница 87: ...d 5VDC 200mA OFF to ON Response 0 5 ms ON to OFF Response 0 5 ms Terminal Type included Removable D2 16IOCON Status Indicator Logic side Weight 2 3 oz 65g Fuses None ZIPLink Module ZL RTB20 Feedthroug...

Страница 88: ...uency N A Minimum Load Current 0 2 mA Max Load Current 0 1 A point 1 6 A module Max Leakage Current 0 1 mA 30VDC Max Inrush Current 150mA for 10ms Base Power Required 5VDC 200mA OFF to ON Response 0 5...

Страница 89: ...Terminal type Removable D2 16IOCON Status indicators Logic Side Weight 2 0 oz 25g Fuses None External DC required 24VDC 10 50mA External DC overvoltage shutdown 27V outputs are restored when voltage...

Страница 90: ...an be reset by turning the assigned output off or power cycling the PLC Example In this example X8 X23 are assigned as fault status indicators X8 Fault status indicator for Y0 X9 Fault status indicato...

Страница 91: ...OFF response 0 5 ms Terminal type Removable D2 16IOCON Status indicators Logic Side Weight 2 0 oz 25g Fuses None External DC required 24VDC 10 50mA External DC overvoltage shutdown 27V outputs are re...

Страница 92: ...ycling the PLC In this example X8 X23 are assigned as fault status indicators X8 Fault status indicator for Y0 X9 Fault status indicator for Y1 X22 Fault status indicator for Y14 X23 Fault status indi...

Страница 93: ...10ms Base Power Required 5VDC 350mA OFF to ON Response 0 5 ms ON to OFF Response 0 5 ms Terminal Type not included Removable 40 pin connector1 Status Indicator Module activity no I O status indicator...

Страница 94: ...g Voltage 12 to 24 VDC Peak Voltage 30VDC ON Voltage Drop 0 5 VDC 0 1 A Minimum Load Current 0 2 mA Max Load Current 0 1 A point 0 8 A common Max Leakage Current 0 1 mA 30VDC Max Inrush Current 150mA...

Страница 95: ...Max Load Current 1 5 A pt 30 C 1 0 A pt 60 C 4 0 A common 8 0 A module 60 C Max Leakage Current 0 7 mA rms Peak One Cycle Surge Current 15A Base Power Required 5VDC 250mA OFF to ON Response 0 5 ms 1 2...

Страница 96: ...5 A point 4A common Max Leakage Current 4mA 264VAC 60Hz 1 2 mA 100VAC 60Hz 0 9 mA 100VAC 50Hz Max Inrush Current 10A for 10ms Base Power Required 5VDC 250mA OFF to ON Response 1ms ON to OFF Response...

Страница 97: ...o n is the starting address Yes Yes Yes Yes Yes Points Yn 10 Yn 11 Yn 12 Yn 13 Yn 14 Yn 15 Yes Used No No 8 Yn Yn 9 Y 0 3 6 9 12 Points 250mA Pt 300mA Pt 0 10 20 30 40 50 55 Ambient Temperature C F 32...

Страница 98: ...wer Required 5VDC 250 mA OFF to ON Response 10ms ON to OFF Response 10ms Terminal Type included Removable D2 8IOCON Status Indicator Logic side Weight 2 8 oz 80g Fuses 1 per point 6 3 A slow blow repl...

Страница 99: ...ncluded Removable D2 8IOCON Status Indicator Logic side Weight 3 9 oz 110g Fuses One 6 3 A slow blow replaceable Order D2 FUSE 3 5 per pack ZIPLink Module ZL RTB20 Feedthrough ZIPLink Cable ZL D2 CBL1...

Страница 100: ...system L L L L L L L L NO1 NO2 NO4 C4 7 NO7 NO0 CO 3 NO3 NO5 NO6 F2 08TR 0 1 2 3 4 5 6 7 OUT RELAY 12 250VAC 10A 50 60Hz 12 28VDC 10mA 10A NO1 NO2 NO4 C4 7 NO7 NO0 CO 3 NO3 NO5 NO6 F2 08TR 0 1 2 3 4...

Страница 101: ...ZL RTB20 Feedthrough ZIPLink Cable ZL D2 CBL19 0 5 m ZL D2 CBL19 1 1 0 m ZL D2 CBL19 2 2 0 m ZL D2 CBL19 1P 1 0 m Pigtail ZL D2 CBL19 2P 2 0 m Pigtail F2 08TRS outputs are derated not to exceed 2 Amp...

Страница 102: ...Module 12 Outputs Points Consumed 16 four unused see chart below Commons per Module 2 6 pts per common Output Type Relay form A SPST Operating Voltage 5 30 VDC 5 240 VAC Peak Voltage 30VDC 264VAC ON V...

Страница 103: ...264VAC ON Voltage Drop N A AC Frequency 47 to 63 Hz Minimum Load Current 5mA 5VDC Max Load Current resistive 1A point 4A module Max Leakage Current 0 1 mA 264VAC Max Inrush Current 3A for 100 ms 10A...

Страница 104: ...Do more H2 Series PLC Hardware User Manual 1st Edition Rev F H2 DM M 5 32 Chapter 5 Specifications Discrete I O Modules 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D Notes...

Страница 105: ...etting the Module Jumpers 6 7 F2 04AD 1 L Addressing 6 8 F2 04AD 2 L Analog Input 6 9 Setting the Module Jumpers 6 10 F2 04AD 2 L Addressing 6 11 F2 08AD 1 Analog Input 6 12 Setting the Module Jumpers...

Страница 106: ...ut 6 41 Setting the Module Jumpers 6 42 F2 4AD2DA Analog Input Output 6 44 Input 6 46 Output 6 46 F2 8AD4DA 1 Analog Input Output 6 47 Input 6 50 Output 6 50 Input Configuration Using Do more Designer...

Страница 107: ...the front panel signifies an Input I O module a red bar signifies an Output I O module and a white bar signifies a combination Input Output module Analog Input Modules Part Number Number of Channels D...

Страница 108: ...DA 1 OUT ANALOG 2CH F2 02DA1 18 30VDC 60mA ANALOG OUT 4 20mA 24V CH1 CH2 NC NC 0V CH1 CH2 NC NC F2 02DA 1 OUT ANALOG A 2CH F2 02DA1 18 30VDC 60mA ANALOG OUT 4 20mA Module Type Red Output Module Part N...

Страница 109: ...ta and setup data X addresses are also assigned to some analog I O modules to indicate the status of those analog I O modules The following table shows how many X WX and WY addresses are assigned to e...

Страница 110: ...12 13 14 A B C D Analog I O Modules Overview continued You can check which X WX and WY addresses are assigned to each analog I O module in the I O Mapping tab of the System Configuration window as sh...

Страница 111: ...elative Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration MIL STD 810C 514 2 Shock MIL STD 810C 516 2 Noise Immunity NEMA ICS3 304 Terminal Type included Removab...

Страница 112: ...o if you only select channels 1 thru 3 channel 4 will not be active The following table shows how to use the jumpers to select the number of channels Unused jumpers can be stored on a single post to p...

Страница 113: ...is removed This address stays off if Channel 2 input is not used Xn 2 On when the external 24VDC input power is missing or terminal block is removed This address stays off if Channel 3 input is not u...

Страница 114: ...514 2 Shock MIL STD 810C 516 2 Noise Immunity NEMA ICS3 304 Terminal Type included Removable D2 8IOCON ZIPLink Module ZL RTB20 Feedthrough ZIPLink Cable ZL D2 CBL10 0 5 m ZL D2 CBL10 1 1 0 m ZL D2 CBL...

Страница 115: ...o prevent losing them As seen above there is also one input signal range jumper labeled J2 or J3 that is used to select between the 5V and 10V signal ranges The module is set from the factory for 10V...

Страница 116: ...en the external 24VDC input power is missing or terminal block is removed This address stays off if Channel 2 input is not used Xn 2 On when the external 24VDC input power is missing or terminal block...

Страница 117: ...rrosive gases permitted Vibration MIL STD 810C 514 2 Shock MIL STD 810C 516 2 Noise Immunity NEMA ICS3 304 Terminal Type included Removable D2 8IOCON ZIPLink Module ZL RTB20 Feedthrough ZIPLink Cable...

Страница 118: ...4 thru eight will not be active The following table shows how to use the jumpers to select the number of channels Unused jumpers can be stored on a single post to prevent losing them F2 08AD 1 Module...

Страница 119: ...24VDC input power is missing or terminal block is removed This address stays off if Channel 4 input is not used Xn 4 On when the transmitter is broken the external 24VDC input power is missing or term...

Страница 120: ...r Supply 5mA maximum 10 to 30 VDC Operating Temperature 32 to 140 F 0 to 60 C Storage Temperature 4 to 158 F 20 to 70 C Relative Humidity 5 to 95 non condensing Environmental Air No corrosive gases pe...

Страница 121: ...seen above there is another jumper labeled J3 that is used to select between the 5V and 10V signal ranges The module is set from the factory for 10V operation jumper not installed F2 08AD 2 Module Ju...

Страница 122: ...ddress stays off if Channel 4 input is not used Xn 4 On when the external 24VDC input power is missing or terminal block is removed This address stays off if Channel 5 input is not used Xn 5 On when t...

Страница 123: ...racy 1 C PLC Update Rate 4 channels per scan maximum Base Power Required 5VDC 90mA Operating Temperature 32 to 140 F 0 to 60 C Storage Temperature 4 to 158 F 20 to 70 C Temperature Drift None self cal...

Страница 124: ...agnitude sign format in Fahrenheit or Celsius Therearetwochannelselectionjumpers labeledCH 1andCH 2 thatareusedtoselectthenumber of channels that will be used The module is set from the factory for fo...

Страница 125: ...e RTD Inputs RTD 0 RTD 1 RTD 2 CU 10q No No No CU 25q Yes No No jPt 100q No Yes No Pt 100q Yes Yes No Pt 1000q No No Yes Yes Jumper Installed No Jumper Removed The last two jumpers Units 0 and Units 1...

Страница 126: ...ed Xn 1 On when the RTD is open or terminal block is removed This address stays off if Channel 2 input is not used Xn 2 On when the RTD is open or terminal block is removed This address stays off if C...

Страница 127: ...2 Shock MIL STD 810C 516 2 Noise Immunity NEMA ICS3 304 Terminal Type included Non removable Thermocouple Specifications Input Ranges Type J 190 to 760 C 310 to 1400 F Type E 210 to 1000 C 346 to 183...

Страница 128: ...tem Note 5 With grounded thermocouples take precautions to prevent having a voltage potential between thermocouple tips A voltage of 5V or greater between tips will skew measurements F2 04THM continue...

Страница 129: ...set from the factory for four channel operation Any unused channels are not processed The following table shows how to use the jumpers to select the number of channels Unused jumpers can be stored on...

Страница 130: ...s The options are 2 s complement in Fahrenheit or Celsius All thermocouple types are converted into a direct temperature reading in either Fahrenheit or Celsius The data contains one implied decimal p...

Страница 131: ...s 0 jumper installed for 2 s complement conversion For Fahrenheit remove Units 1 jumper For Celsius remove both Units 0 and Units 1 jumpers The Calibrate Enable jumper J9 comes from the factory in the...

Страница 132: ...is module F2 04THM X Addressing Address Description Xn On when the thermocouple is open or the external 24VDC input power is missing Xn 1 On when the thermocouple is open or the external 24VDC input p...

Страница 133: ...uding maximum offset change of 2 counts Maximum Inaccuracy 0 1 77 F 25 C 0 3 32 to 140 F 0 to 60 C Base Power Required 5VDC 40mA External Power Supply F2 02DA 1 18 to 30VDC 60mA F2 02DA 1L 10 to 15VDC...

Страница 134: ...4 5 6 7 8 9 10 11 12 13 14 A B C D F2 02DA 1 L Analog Output continued The Do more CPU module assigns the following memory addresses to this module WYn Starting WY address assigned to this module F2 0...

Страница 135: ...0 55 bipolar ranges 77 F 25 C Base Power Required 5VDC 40mA External Power Supply F2 02DA 2 18 to 30VDC 60mA outputs fully loaded F2 02DA 2L 10 to 15VDC 70mA outputs fully loaded Operating Temperatur...

Страница 136: ...rd jumpers are labeled UNI and there is one for each channel These jumpers determine the format of the channel output data and the effect of their settings is independent from that of the other jumper...

Страница 137: ...ange the jumpers as follows Install the CH1 UNI 5V jumper Remove the CH1 UNI jumper Store the jumper so it does not get lost by placing it on one pin Install the CH1 BI P 0 5 jumper in the BI P bipola...

Страница 138: ...D The Do more CPU module assigns the following memory addresses to this module F2 02DA 2 L Analog Output continued WYn Starting WY address assigned to this module F2 02DA 2 L WY Addressing Address De...

Страница 139: ...ontinuous channel to channel channel to logic Base Power Required 5VDC 100mA Loop Supply 18 32 VDC External Power Supply 18 32 VDC 50mA per channel Output Loop Compliance Vin 2 5 V Load Impedance 0 13...

Страница 140: ...es is Signed Word They store 32768 to 32767 as default To read and write 0 to 65535 into these memory addresses use the casting U U is the casting for Unsigned format For instance if WY0 is assigned t...

Страница 141: ...ling Time 3ms to 0 1 of full scale Linearity Error end to end 10 count 0 015 of full scale maximum Gain Calibration Error 32 counts 0 05 Offset Calibration Error 13 counts 0 02 Output Drift 50ppm C Ma...

Страница 142: ...move these jumpers to select the desired range See the figures below to find the jumpers on your module The module is set from the factory for the 0 5 V range Refer to the following table in order to...

Страница 143: ...es is Signed Word They store 32768 to 32767 as default To read and write 0 to 65535 into these memory addresses use the casting U U is the casting for Unsigned format For instance if WY0 is assigned t...

Страница 144: ...NEMA ICS3 304 Terminal Type included Removable D2 16IOCON ZIPLink Module ZL RTB20 Feedthrough ZIPLink Cable ZL D2 CBL19 0 5 m ZL D2 CBL19 1 1 0 m ZL D2 CBL19 2 2 0 m ZL D2 CBL19 1P 1 0 m Pigtail ZL D2...

Страница 145: ...g memory addresses to this module F2 08DA 1 WY Addressing Address Description WYn Channel 1 Output Data 0 to 4095 WYn 1 Channel 2 Output Data 0 to 4095 WYn 2 Channel 3 Output Data 0 to 4095 WYn 3 Chan...

Страница 146: ...nversion Settling Time 400 s maximum full scale change 4 5 ms to 9ms for digital out to analog out Linearity Error end to end 1 count 0 025 of full scale maximum Full Scale Calibration Error 12 counts...

Страница 147: ...ect between the 0 5 V or 0 10 V operating ranges Refer to the following figure and table for proper selection of voltage range The output data format remains 0 4095 for either voltage range selected U...

Страница 148: ...g memory addresses to this module F2 08DA 2 WY Addressing Address Description WYn Channel 1 Output Data 0 to 4095 WYn 1 Channel 2 Output Data 0 to 4095 WYn 2 Channel 3 Output Data 0 to 4095 WYn 3 Chan...

Страница 149: ...910q 24V current outputs 620q 18V 1200 q 30 V Active Low pass Filter 3dB 20Hz 2 poles 12dB per octave Linearity Error best fit 1 count 0 025 of full scale maximum Output Settling Time 100 s maximum f...

Страница 150: ...ower supply commons are connected Note 4 A Series 217 0 032A fast acting fuse is recommended for 4 20 mA current input loops Note 5 f the power supply common of an external power supply is not connect...

Страница 151: ...oved Xn 1 On when the external 24VDC input power is missing or terminal block is removed Xn 2 On when the external 24VDC input power is missing or terminal block is removed Xn 3 On when the external 2...

Страница 152: ...utput Protection Electronically current limited to 20mA or less Output Signal at Power up and Power down 4mA Terminal Type included Removable D2 16IOCON ZIPLink Module ZL RTB20 Feedthrough ZIPLink Cab...

Страница 153: ...tter 3 wire 4 20mA COM 100 I3 100 100 100 CH5 ADC COM Note 1 A Littlefuse Series 217 0 032A fast acting fuse is recommended for all 4 20mA current loop inputs Note 2 Connect shields to the 0V of the m...

Страница 154: ...wer is missing or terminal block is removed Xn 1 On when the transmitter is broken the external 24VDC input power is missing or terminal block is removed Xn 2 On when the transmitter is broken the ext...

Страница 155: ...ng U U is the casting for Unsigned format For instance if WY0 is assigned to the first analog output channel use WY0 U to access this memory address in the ladder program and other tools in Do more De...

Страница 156: ...aximum or Reset held value or each input can be individually disabled From the System Configurations page select Module Configuration s in the tab on the left The screen below will appear showing the...

Страница 157: ...dule Two 2 bits in this memory address are assigned to each analog input channel The HEX data format is used to set up the input resolution as seen in the following example Example An F2 8AD4DA 1 is i...

Страница 158: ...The HEX data format is used to set up the track and hold option as seen in the following example Example An F2 8AD4DA 1 is installed in slot 0 and WY6 is used for the track and hold selection Input ch...

Страница 159: ...tion 1VDC peak output voltage clamped by transient voltage suppressor Output Signal at Power up and Power down 0V Terminal Type included Removable D2 16IOCON ZIPLink Module ZL RTB20 Feedthrough ZIPLin...

Страница 160: ...Isolated analog circuit common Voltage transmitter transmitter 3 wire voltage COM V3 CH5 ADC COM Note 1 Connect shields to the 0V of the module do not connect both ends of shield CH1 DAC CH2 DAC COM C...

Страница 161: ...t resolution for the first analog input channel and WX0 is assigned to the channel use WX0 U to access this memory address in the ladder program and other tools in Do more Designer Xn Starting X addre...

Страница 162: ...e casting for Unsigned format For instance if WY0 is assigned to the first analog output channel use WY0 U to access this memory address in the ladder program and other tools in Do more Designer WYn S...

Страница 163: ...value or each input can be individually disabled Input and output ranges can also be configured for 0 to 5V or 0 to 10V in this section From the System Configurations page select Module Configuration...

Страница 164: ...dule Two 2 bits in this memory address are assigned to each analog input channel The HEX data format is used to set up the input resolution as seen in the following example Example An F2 8AD4DA 2 is i...

Страница 165: ...is stored in memory address WYn 5 WYn Starting WY address assigned to this module Only 2 bits in this memory address are used for the setup The HEX data format is used to set up the input resolution...

Страница 166: ...The HEX data format is used to set up the track and hold option as seen in the following example Example An F2 8AD4DA 2 is installed in slot 0 and WY6 is used for the track and hold selection Input ch...

Страница 167: ...H2 CTRIO 2 Input Wiring Examples 7 10 TTL Quadrature Encoder Field Wiring 7 10 TTL Input Wiring Example 7 10 Quadrature Encoder Wiring Example 7 11 NPN Open Collector Device 7 11 PNP Open Collector D...

Страница 168: ...BC100 Specifications 7 22 H2 EBC100 LED Indicators 7 23 H2 ERM 100 H2 EBC100 Network Identifiers 7 23 H2 ERM 100 H2 EBC100 Network Layouts 7 26 H2 ERM 100 H2 EBC100 Network Cabling 7 27 H2 SERIO 4 7 2...

Страница 169: ...cators can show the network health module health I O status or mode of operation the module is currently in Module Type White Specialty Module Part Number Specialty Modules Part Number Description See...

Страница 170: ...unication Module H2 EBC F 10 Base FL Ethernet Base Controller H2 ECOM100 100 Base T Ethernet Communication Module H2 SERIO Serial I O Module H2 ECOM F 10 Base FL Ethernet Communication Module H2 SERIO...

Страница 171: ...r a combination of both high speed input and high speed output control functions The H2 CTRIO 2 module has its own internal microprocessor and operates asynchronously with respect to the CPU Therefore...

Страница 172: ...nfigure the input and output functions of the selected module Refer to the Do more Designer Help File for more information on configuration options The above window can be accessed once the H2 CTRIO2...

Страница 173: ...2 0 mA OFF to ON Response less than 3 s less than 0 5 s ON to OFF Response less than 3 s less than 0 5 s Output Specifications Specifications H2 CTRIO H2 CTRIO2 Outputs 4 pts sink source independentl...

Страница 174: ...put is passing current CTR IN OK ER 1A 2A 0 1 2 3 H2 CTRIO 24 VDC OUTPUTS 2A 2B 2C 2D 2M C2 Y2 C3 Y3 1A 1B 1C 1D 1M NC C0 Y0 C1 Y1 IN 9 30 VDC 5 12 mA OUT 5 36 VDC 1 0Amax per point CTR IN OK ER 1A 2A...

Страница 175: ...opriate Y0 Y1 Install jumper s to internally connect Y0 to other Y terminals in order to reduce wiring if appropriate Connect wire at Y0 Y0 Y2 Y0 Y3 C0 C1 Install jumper s to internally connect C0 to...

Страница 176: ...te wiring to avoid any runs parallel to noisy cables Route wiring to avoid the proximity of noisy devices Use shielded twisted pair cables such as 24VDC 1A 1M Sensing Circuit This drawing illustrates...

Страница 177: ...0 V Black OUT A Purple OUT A White OUT B Gray OUT B Orange OUT Z Yellow OUT Z Shield Ground Differential Line Driver Encoder Use separate power supply to maintain isolation CTR IN 24 VDC OUTPUTS IN 9...

Страница 178: ...2 Y 3 C 3 Y M 2 A B Z 9 30VDC 9 30VDC Power Gnd A B Z Power Gnd NPN Open Collector PNP Open Collector or Totem Pole Quadrature Encoder Wiring Example NPN Open Collector Device Encoder Shield twisted p...

Страница 179: ...a standard method but you must consult your step amplifier documentation to ensure that this method is applicable 5 to 36VDC CTRIO Output Cn where n 0 1 2 3 Yn where n 0 1 2 3 Load 5 to 36VDC Load CT...

Страница 180: ...and MODBUS TCP IP devices is accomplished by using the MRX MWX instructions You can use a personal computer equipped with a 10 100BaseT network adapter card and NetEdit3 software to configure the ECO...

Страница 181: ...ON Green Properly connected to network OFF Not connected to network or incorrect configuration ACTIVE ON or FLASHING Red Active Network Data OFF Network Idle ERROR ON or FLASHING Red A fatal error ha...

Страница 182: ...e diagram below The Name can be up to 32 alphanumeric characters in length NOTE Some HMI software products will not accept Names with numbers as the first character spaces or certain other non alphanu...

Страница 183: ...ddresses must match the first two fields of the Client IP or 192 168 The last two fields are allowed to vary because they are masked with a 0 WARNING It is extremely important not to have duplicate IP...

Страница 184: ...mmunication with the PC An ECOM can sequence through communication connections with each PLC on the network one at a time The ECOM products inherently support two network layouts point to point and st...

Страница 185: ...tch straight through cable The cable used to connect together two PLCs a PC and a PLC or two switches is a crossover cable We recommend that you purchase cables pre assembled with connectors for conve...

Страница 186: ...Therefore it is not possible to state an absolute maximum number of nodes that would apply in all cases The IEEE 802 3 specification defines the maximum node limit for an Ethernet segment in terms of...

Страница 187: ...ECOM modules you can access from the NetEdit3 or Do more Designer software There is a node limit for PLC to PLC communications The network Read and Write instructions performed by the initiating maste...

Страница 188: ...pand the number of nodes The PLC ERM and EBC slave modules work together to update the remote I O points These three scan cycles are occurring at the same time but asynchronously Critical I O points t...

Страница 189: ...odule supports industry standard 10 100BaseT Ethernet and Ethernet IP communications NOTE The RS 232 serial port on the EBC module cannot be used when the EBC module is part of the Do more controller...

Страница 190: ...ERM to 0 Module ID can be changed without NetEdit3 When set disables Module ID selection in NetEdit3 NetEdit3 Slave Number 1 65535 Set ERM to 0 DIP Switch must be set to 0 IP Address UDP IP NetEdit3 4...

Страница 191: ...le if slide switches 1 2 and 3 are set to the ON position the Module ID will be 14 This is found by adding 8 4 2 14 The maximum value which can be set on the DIP switch is 32 16 8 4 2 63 This is achie...

Страница 192: ...55 fields If any field contains the number 255 and other fields have been changed the module will not be recognized on the network Example IP Addresses 192 168 55 5 Valid IP Address 255 168 55 5 Not V...

Страница 193: ...he ERM module and its slaves over the Ethernet remote I O network Once the ERM I O network is configured and running the PC can be removed from the network 405EBC POWER ERROR RELAY LINK GOOD ACTIVITY...

Страница 194: ...ch is called a patch straight through cable The cable used to connect together two PLCs a PC and a PLC or two switches is a crossover cable We recommend that you purchase cables pre assembled with con...

Страница 195: ...12 13 14 A B C D The maximum distance per 10 100BaseT cable segment is 100 meters or 328 feet Switches allow multiple 100 meter cable segments to be joined together increasing the allowable distance F...

Страница 196: ...n to setup the port to work with the Do more Designer programming software K Sequence Select this option to have the port respond to client devices running K Sequence protocol Modbus RTU Server Select...

Страница 197: ...M 7 31 Chapter 7 Specifications Specialty Modules 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D These parameters can also be set programmatically using the SETUPSER instruction seen here See the Do more He...

Страница 198: ...422 ADC L19853 x Belden 8103 RS 485 ADC L19954 x Belden 9842 Protocols Supported Serial ASCII full duplex K Sequence Modbus RTU and Do more programming Power Consumption 80mA 5VDC Baud Rates 1200 240...

Страница 199: ...ate or deactivate resistor GND RX RX TX TX Slave 2 D RXD D RXD Set DIP switch S2 on the H2 SERIO 4 to 1 Activate or deactivate the internal 120 termination resistor 2 Select RS 422 or RS 485 operation...

Страница 200: ...alty Modules 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D F2 08SIM Input Simulator F2 08SIM Specifications F2 08SIM Input Simulator Inputs per Module 8 Base Power Required 5VDC 50mA Terminal Type None Sta...

Страница 201: ...se Dimensions 8 5 Panel Mounting and Layout 8 6 Enclosures 8 7 Environmental Specifications 8 8 Marine Use 8 8 Agency Approvals 8 8 24VDC Power Bases 8 8 Installing Bases for Do more 8 9 Mounting the...

Страница 202: ...es 8 17 Powering I O Circuits with the Auxiliary Supply 8 18 Powering I O Circuits Using Separate Supplies 8 19 Sinking Sourcing Concepts 8 20 I O Common Terminal Concepts 8 21 Connecting DC I O to So...

Страница 203: ...ts should be designed using simple logic with a minimum number of highly reliable electromechanical components Every automation application is different so there may be special requirements for your p...

Страница 204: ...should be easily accessed by the operator and are generally wired into a master control relay MCR or a safety control relay SCR that will remove power from the PLC I O system in an emergency MCRs and...

Страница 205: ...ally the first level of fault detection is the PLC control program which can identify machine problems Certain shutdown sequences should be performed The types of problems are usually things such as j...

Страница 206: ...tion shows the proper mounting dimensions The height dimension is the same for all bases The depth varies depending on your choice of I O module The length varies as the number of slots increase Make...

Страница 207: ...provide proper ventilation 2 If you place more than one base in a cabinet there should be a minimum of 7 2 in 183mm between bases 3 Provide a minimum clearance of 2in 50mm between the base and all si...

Страница 208: ...rature may approach the lower or upper limits of the specifications Place a temperature probe in the panel close the door and operate the system until the ambient temperature has stabilized If the amb...

Страница 209: ...s which your application may require are UL Underwriters Laboratories Inc CSA Canadian Standards Association FM Factory Mutual Research Corporation cUL Canadian Underwriters Laboratories Inc 24VDC Pow...

Страница 210: ...ils are approximately 35mm high with a depth of 7 5 mm If you mount the base on a rail you should also consider using end brackets on each end of the rail The end brackets help keep the base from slid...

Страница 211: ...he module is inserted into the base push in the retaining clips to firmly secure the module to the base WARNING To minimize the risk of electrical shock personal injury or equipment damage always disc...

Страница 212: ...the recommended size Do not overtighten the connector screws the recommended torque value is 7 81 lb in 0 882 N m NOTE You can connect either a 115VAC or 220VAC supply to the AC terminals without the...

Страница 213: ...troller and is not numbered Module Placement Restrictions The following table lists the valid locations for all types of modules in a Do more system Module Unit Local CPU Base Ethernet Remote I O Base...

Страница 214: ...sily removed If you examine the connectors closely you ll notice there are squeeze tabs on the top and bottom To remove the terminal block press the squeeze tabs and pull the terminal block away from...

Страница 215: ...where possible 5 Avoid running wires near high energy wiring Also avoid running input wiring close to output wiring where possible 6 To minimize voltage drops when wires must run a long distance cons...

Страница 216: ...dule Cable F2 04AD 1 10 Feedthrough ZL RTB20 ZL D2 CBL10 F2 08AD 1 10 Feedthrough ZL RTB20 ZL D2 CBL10 F2 04AD 2 10 Feedthrough ZL RTB20 ZL D2 CBL10 F2 08AD 2 10 Feedthrough ZL RTB20 ZL D2 CBL10 F2 02...

Страница 217: ...D2 CBL19 Fuse ZL RFU204 ZL D2 CBL19 D2 04TRS 10 Feedthrough ZL RTB20 ZL D2 CBL10 D2 08TR 10 Feedthrough ZL RTB20 ZL D2 CBL10 F2 08TRS 19 Feedthrough ZL RTB20 ZL D2 CBL19 F2 08TR 10 Feedthrough ZL RTB2...

Страница 218: ...crete inputs are isolated from the discrete outputs because each is isolated from the logic side Isolation boundaries protect the operator interface and the operator from power input faults or field w...

Страница 219: ...y supply If input devices AND output loads need 24VDC power the auxiliary supply may be able to power both circuits as shown in the following diagram The 12 24VDC powered bases are designed for applic...

Страница 220: ...ions will use the PLC external power source to also power the input circuit This typically occurs on DC powered PLCs as shown in the drawing below to the left The inputs share the PLC power source sup...

Страница 221: ...le to connect the external supply and field device to the I O point with current trying to flow in the wrong direction and the circuit will not operate However you can successfully connect the supply...

Страница 222: ...hare a common return path In this way the four inputs require only five terminals instead of eight NOTE In the circuit above the current in the common path is 4 times any channel s input current when...

Страница 223: ...n be the 24 auxiliary supply or another supply 12 VDC or 24VDC as long as the input specifications are met In the above circuit a field device has an open collector PNP transistor output It sources cu...

Страница 224: ...rehend this and generate an inverted output Or you may choose to cancel the effect of the inversion elsewhere such as in the field device It is important to choose the correct value of Rpull up In ord...

Страница 225: ...uire currents under 10mA Loads which must be switched at high speed or heavy duty cycle Relay outputs in the Do more output modules are available in two contact arrangements shown to the right The For...

Страница 226: ...s opened thereby de energizing the coil the transient voltage generated across the switch contacts peaks at 140V In the same circuit replacing the relay with a larger 24V 290mA 7W relay will generate...

Страница 227: ...range for some time the 40V is still beyond the module s peak output voltage rating of 30V 5HOD RLO 9 2VFLOORVFRSH RU WKLV H DPSOH D 9 P UHOD LV XVHG XWRPDWLRQ LUHFW SDUW QR 9ROWV Example Small Induct...

Страница 228: ...ope 24 VDC DC Flyback Circuit Sinking Sourcing _ 30 25 20 15 10 5 0 5 Volts Many AutomationDirect socketed relays and motor starters have add on flyback diodes that plug or screw into the base such as...

Страница 229: ...check the suppressor ratings Just because the suppressor is made specifically for that part does not mean it will reduce the transient voltages to an acceptable level For example a MOV or TVS diode ra...

Страница 230: ...Do more H2 Series PLC User Manual 1st Edition Rev F H2 DM M 8 30 Chapter 8 Installation and Wiring 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D Notes...

Страница 231: ...Do more Product Weight Table A A A Appendix Appendix Appendix In This Appendix Do more Product Weight Table A 2...

Страница 232: ...80g D2 08TD1 2 3 oz 65g D2 08TD2 2 1 oz 60g D2 16TD1 2 2 3 oz 65g D2 16TD2 2 2 8 oz 80g F2 16TD1P 2 0 oz 56g F2 16TD2P 2 0 oz 56g D2 32TD1 2 1oz 60g D2 32TD2 2 1 oz 60g AC Output Modules D2 08TA 2 8...

Страница 233: ...European Union Directives CE Appendix Appendix Appendix B B In This Appendix European Union EU Directives B 2 Basic EMC Installation Guidelines B 5...

Страница 234: ...alta Netherlands Poland Portugal Romania Slovakia Slovenia Spain Sweden and United Kingdom Iceland Liechtenstein and Norway together with the EU members make up the European Economic Area EEA and all...

Страница 235: ...al commercial and light industry EN50082 2 Generic immunity standard for industrial environment Low Voltage Directive Standards Applicable to PLCs EN61010 1 Safety requirements for electrical equipmen...

Страница 236: ...rictions on the control panel builder Because of these additional requirements it is recommended that the following publications be purchased and used as guidelines BSI publication BS TH 42073 Novembe...

Страница 237: ...d like to point out that although our products operate normally in the presence of ESD this is only the case when mounted within an enclosed industrial control cabinet When the cabinet is open during...

Страница 238: ...l supplies 150VAC working voltage for 115V supplies and high energy capacity eg 140 joules Transient suppressors must be protected by fuses and the capacity of the transient suppressor must be greater...

Страница 239: ...ices connected to the PLC The diagram shows an example of four physical locations connected by a communications cable Communications and Shielded Cables Good quality 24 AWG minimum twisted pair shield...

Страница 240: ...n provided in the past by the cable shield It is now recommended that you use triple twisted pair cabling for RS422 links and twin twisted pair cable for RS485 links This is because the extra pair can...

Страница 241: ...g maintenance so that remote commands cannot be received that could result in the operation of the machinery The FA ISOCON does not have a keyswitch Use a keylock and switch on your enclosure which wh...

Страница 242: ...n a protective steel enclosure which limits access to operators by a lock and power breaker If access is required by operators or untrained personnel the equipment must be installed inside an internal...

Отзывы: