6–40
Chapter 6: Specifications - Analog I/O Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2–08DA–1, Analog Output
Note 1: Shields should be connected to the 0V of the module.
Offset Calibration Error
±9 counts max. sinking @ any load
±9 counts max. sourcing @ 125
q
load
±11 counts max. sourcing @ 250
q
load
±13 counts max. sourcing @ 400
q
load
Maximum Full Scale
Inaccuracy @ 60ºC
0.5% sinking (any load) sinking &
sourcing @ 125
q
load
0.64% sourcing @ 250
q
load
0.83% sourcing @ 400
q
load
Maximum Full Scale
Inaccuracy @ 25ºC
(Incudes all errors and temp drift)
0.3% sinking (any load) sinking &
sourcing @ 125
q
load
0.44% sourcing @ 250
q
load
0.63% sourcing @ 400
q
load
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4 to 158ºF(-20 to 70ºC)
Relative Humidity
5% to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-16IOCON
ZIPLink Module
ZL-RTB20 (Feedthrough)
ZIPLink Cable
ZL-D2-CBL19 (0.5 m)
ZL-D2-CBL19-1 (1.0 m)
ZL-D2-CBL19-2 (2.0 m)
ZL-D2-CBL19-1P (1.0 m Pigtail)
ZL-D2-CBL19-2P (2.0 m Pigtail)
F2-08DA-1 8-Channel Analog Current Output
Number of Channels
8, single-ended
Output Ranges
4 to 20mA
Resolution
12 bit (1 in 4096)
Output Type
Current sinking or current sourcing
Base Power Required
5VDC
30mA
Maximum Loop Voltage
30VDC
External Power Supply
18 to 30VDC, 50mA., class 2
(Add 20mA for each current loop used)
Source Load
0–400
q
@ 18–30 VDC
Sink Load
0–600
q
/18V, 0–900
q
/24V, 0–1200
q
/30V
Total Load
(sink + source)
600
q
/18V, 900
q
/24V, 1200
q
/30V
PLC Update Rate
8 channels per scan maximum
Conversion Settling Time
400µs maximum (full scale change)
Linearity Error
(end to end)
±2 count (±0.050% of full scale) maximum
Full Scale Calibration
Error
±12 counts max. sinking @ any load
±12 counts max. sourcing @ 125
q
load
±18 counts max. sourcing @ 250
q
load
±26 counts max. sourcing @ 400
q
load
OUT
F2-08DA-1
ANALOG
8 CHANNEL
18-26.4VDC
80mA
4-20mA
SNK-SRC
1-O
2-O
3-O
4-O
5-O
6-O
7-O
8-O
0V
1-I
2-I
3-I
4-I
5-I
6-I
7-I
8-I
N/C
24V
Содержание Do-more H2 PLC Series
Страница 2: ...Notes...
Страница 6: ...Notes...
Страница 8: ...Notes...
Страница 231: ...Do more Product Weight Table A A A Appendix Appendix Appendix In This Appendix Do more Product Weight Table A 2...