Do-more H2 Series PLC Hardware User Manual, 1st Edition, Rev. F - H2-DM-M
4–7
Chapter 4: Specifications - Base Units
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Power Requirements
The charts below show the amount of power supplied by each of the base power supplies and
the amount of power consumed by each module. The Power Consumed charts list how much
INTERNAL power from each power source is required for the modules. Use this information
when calculating the power budget for your system.
In addition to the internal power sources, bases offer a 24VDC auxiliary power supply with
external power connections. This auxiliary power supply can power external devices.
Power Consumed
Device
5V(mA) 24V Auxiliary
CPUs
H2-DM1
250
0
H2-DM1E
275
0
DC Input Modules
D2-08ND3
50
0
D2-16ND3-2
100
0
D2-32ND3
25
0
D2-32ND3-2
25
0
AC Input Modules
D2-08NA-1
50
0
D2-08NA-2
100
0
D2-16NA
100
0
DC Output Modules
D2-04TD1
60
20
D2-08TD1
100
0
D2-08TD2
100
0
D2-16TD1-2
200
80
D2-16TD2-2
200
0
F2-16TD1P
70
50
F2-16TD2P
70
50
D2-32TD1
350
0
D2-32TD2
350
0
Power Supplied
Device
5V(mA) 24V Auxiliary Device
5V(mA) 24V Auxiliary
Bases
Bases
D2-03B-1
2600
300
D2-04BDC1-1 2600
None
D2-04B-1
2600
300
D2-06BDC1-1 2600
None
D2-06B-1
2600
300
D2-09BDC1-1 2600
None
D2-09B-1
2600
300
D2-06BDC2-1 2600
300
D2-03BDC1-1 2600
None
D2-09BDC2-1 2600
300
Power Consumed
Device
5V(mA) 24V Auxiliary
AC Output Modules
D2-08TA
250
0
F2-08TA
250
0
D2-12TA
350
0
Relay Output Modules
D2-04TRS
250
0
D2-08TR
250
0
F2-08TR
670
0
F2-08TRS
670
0
D2-12TR
450
0
Combination In/Out Module
D2-08CDR
200
0
Analog Modules
F2-04AD-1
100
5
F2-04AD-2
110
5
F2-08AD-1
100
5
F2-08AD-2
100
5
F2-02DA-1
40
60 (note 1)
F2-02DA-1L
40
70 @ 12V (note 1)
F2-02DA-2
40
60
F2-02DA-2L
40
70 @ 12V
F2-02DAS-1
100
50 / channel
Power Consumed
Device
5V(mA) 24V Auxiliary
Analog Modules (continued)
F2-02DAS-2
100
60 / channel
F2-08DA-1
30
50 (note 1)
F2-08DA-2
60
140
F2-4AD2DA
60
80 (note 1)
F2-8AD4DA-1 35
100 (note 1)
F2-8AD4DA-2 35
80 (note 1)
F2-04RTD
90
0
F2-04THM
110
60
Specialty Modules
H2-CTRIO
2
400
0
H2-CTRIO2
275
0
H2-EBC100
300
0
H2-EBC-F
640
0
H2-ECOM100 300
0
H2-ECOM-F
640
0
H2-ERM(100) 320(300)
0
H2-ERM-F
450
0
H2-SERIO
80
0
H2-SERIO-4
80
0
F2-08SIM
50
0
1: Add an additional 20mA per output loop.
2: H2-CTRIO has been discontinued, use H2-CTRIO2.
Содержание Do-more H2 PLC Series
Страница 2: ...Notes...
Страница 6: ...Notes...
Страница 8: ...Notes...
Страница 231: ...Do more Product Weight Table A A A Appendix Appendix Appendix In This Appendix Do more Product Weight Table A 2...