Chapter 6: Specifications - Analog I/O Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-04THM - continued
Setting the Module Jumpers
There are eight jumpers (J7) and one single jumper (J9) located on the PC board of this
module. These jumpers configure the module for the following options:
• Number of channels
• Input type
• Thermocouple or Voltage conversion units
• Calibrate enable
There are two channel selection
jumpers, labeled CH+1 and CH+2, that are used to select the number of channels that will be
used. The module is set from the factory for four channel operation. Any unused channels
are not processed. The following table shows how to use the jumpers to select the number of
channels. Unused jumpers can be stored on a single post to prevent losing them.
F2-04THM Module Jumper Table (Channel)
Number of Channels
Active Channels
CH+1
CH+2
One
Channel 1
No
No
Two
Channels 1 and 2
Yes
No
Three
Channels 1, 2 and 3
No
Yes
Four
Channels 1, 2, 3 and 4
Yes
Yes
Yes = Jumper Installed
No = Jumper Removed
Calibrate Enable
UNITS-1
UNITS-0
TcTYPE2
TcTYPE3
TcTYPE1
TcTYPE0
CH+2
CH+1
Calibrat
e
Enable Calibrat
e
Enable
UNITS-1
UNITS-0
TcTYPE2
TcTYPE3
TcTYPE1
TcTYPE0
CH+2
CH+1
Calibrate Enable
Jumper Location on Modules Having
Two Circuit Board Design
Jumper Location on Modules Having
Single Circuit Board Design