Do-more H2 Series PLC User Manual, 1st Edition, Rev. F - H2-DM-M
6–28
Chapter 6: Specifications - Analog I/O Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-04THM - continued
The Do-more CPU module assigns the following memory addresses to this module.
NOTE 1:
The data format of the WX addresses is ‘Signed Word’. They store -32768 to 32767 as default.
To read and write 0 to 65535 into these memory addresses, use the casting ‘:U’ (‘:U’ is the casting for
‘Unsigned’ format). For instance, if you selected the voltage input for the first analog input channel and
WX0 is assigned to the channel, use ‘WX0:U’ to access this memory address in the ladder program and
other tools in Do-more Designer.
Xn: Starting X address assigned to this module
WXn: Starting WX address assigned to this module
F2-04THM X Addressing
Address
Description
Xn
On when the thermocouple is open or the external 24VDC input power is missing.
Xn+1
On when the thermocouple is open or the external 24VDC input power is missing.
(This address stays off if Channel 2 input is not used)
Xn+2
On when the thermocouple is open or the external 24VDC input power is missing.
(This address stays off if Channel 3 input is not used)
Xn+3
On when the thermocouple is open or the external 24VDC input power is missing.
(This address stays off if Channel 4 input is not used)
Xn+4
Not used
Xn+5
Not used
Xn+6
Not used
Xn+7
Not used
F2-04THM WX Addressing
Address
Description
WXn
Channel 1 Input Data (Temperature [Unit: 0.1 degree] or Voltage [0 to 65535
1
])
WXn+1
Channel 2 Input Data (Temperature [Unit: 0.1 degree] or Voltage [0 to 65535
1
])
WXn+2
Channel 3 Input Data (Temperature [Unit: 0.1 degree] or Voltage [0 to 65535
1
])
WXn+3
Channel 4 Input Data (Temperature [Unit: 0.1 degree] or Voltage [0 to 65535
1
])