The electrical connection of both end switches for the positions „gate open“ and „gate closed“ are
shown in Section „4.3.6“ of this document. The gate‘
s end switches are connected and checked as
follows during setup:
-
Steuerung spannungsfrei schalten.
-
Beide Endschalter in den jeweiligen Endlagen des Tores mechanisch montieren.
-
Signalleitung vom Endschalter ZU an die Klemme IN1 anschließen.
-
Signalleitung vom Endschalter AUF an die Klemme IN2 anschließen.
-
Stromversorgung der Steuerung einschalten und den korrekten Anschluss der
Endschalter
mit der Anzeige „
Sensordarstellung
“ und die Reaktion
en des Tores im
„Totmannbetrieb“ prüfen!
The control system is now also able to function with end switches.
6.2.6
Programming the gate‘s runtime between the end positions
The control system must measure the motor runtime between the gate‘s end positions with a
reference run so that the drive motor can reduce its maximum speed shortly before reaching the
end switches. It can then estimate the gate‘s pathway using the runtime with the respective end
switch as reference point and can move more slowly into the gate‘s end positions. This reference
run can be initiated in the following ways:
-
Menu: „Service Menu“, „Password Input“: Enter password
-
Menu: „Settings“, „Safeties“, “Learn Limits”: set the value to ‘2’
-
Menu: „Settings“, „Operating Mode“, „Automatic Mode“
-
Quit menu. The control system executes a reset and is in automatic operation
-
Press CLOSE button. Gate moves in the direction of the CLOSE position
-
The gate stops when the CLOSE end switch is reached and automatically moves in
the OPEN direction. The gate stops again upon reaching the OPEN end switch and
saves the measured motor runtime. The control system then executes a reset.
-
Check the slower approach of both end positions and the motor stop once the end
positions are reached!
Attention
: The programming of the motor runtime must always start first with the approach of
the CLOSE position. The runtime is measured from the CLOSE position to the OPEN position.
The control system is then functionable in automatic operation.
6.3 Additional function parameters
With the settings from Chap. 6.2 everything has been done to safely operate the gate.
Furthermore, numerous other installations and configurations of the control system are possible.
All configurations and displays that can only be accessed by a trained technician are protected
with a password.
6.3.1 Setting the language
The technician can specifically switch the control system - which normally runs in automatic
operation - to deadman operation. The gate can then only be activated with the connected
deadman buttons for the OPEN and CLOSE directions (IN8 and IN7). The external safety devices
(safety contact edges and light barrier) are deactivated in the process.
-
Menu: „Service Menu“, „Password Input“: Enter password
-
Menu: „Service Menu“, „Language“: Select national language
-
The display is immediately shown in the new language once the language has been
selected