As can be seen in the image below, the example application has connected the three phase currents
and the residual current (I01). The digital inputs are connected to indicate the breaker status, while the
digital outputs are used for breaker control.
Figure. 7.2 - 176. Application example and its connections.
7.3 Two-phase, three-wire ARON input connection
This chapter presents the two-phase, three-wire ARON input connection for any AQ-200 series IED
with a current transformer. The example is for applications with protection CTs for just two phases. The
connection is suitable for both motor and feeder applications.