Instruction manual
–
AQ F3x0 Feeder protection IED
98 (162
)
Table 3-49: The binary output status signals of the dead line detection function
Table 3-50Setting parameters of the dead line detection function
Parameter
Setting value, range
and step
Description
Operation
On
Off
Operating mode selection for the function. Operation can be
either disabled
“
Off
”
or enabled
“
On
”
. Default setting is
enabled.
Min. operate
voltage
10
…
100 % by step of
1 %
Minimum voltage threshold for detecting the live line status.
All measured phase to ground voltages have to be under this
setting level. Default setting is 60 %.
Min. operate
current
8
…
100 % by step of
1 %
Minimum current threshold for detecting the dead line status.
If all the phase to ground voltages are under the setting
“
Min.
operate voltage
”
and also all the phase currents are under
the
“
Min. operate current
”
setting the line status is considered
“
Dead
”
. Default setting is 10 %.
3.3.4
V
OLTAGE TRANSFORMER SUPERVISION
(VTS)
The voltage transformer supervision function generates a signal to indicate an error in the
voltage transformer secondary circuit. This signal can serve, for example, a warning,
indicating disturbances in the measurement, or it can disable the operation of the distance
protection function if appropriate measured voltage signals are not available for a distance
decision.
The voltage transformer supervision function is designed to detect faulty asymmetrical
states of the voltage transformer circuit caused, for example, by a broken conductor in the
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...