Current transformer supervision function CTS
Pick-up starting inaccuracy at In
<2%
Minimum operation time
70ms
Reset ratio
0.95
Sag and swell (Voltage variation)
Voltage measurement inaccuracy
±
1% of Un
Timer inaccuracy
±2% of setting value or
±20ms
Dead line detection DLD
Pick-up voltage inaccuracy
1%
Operation time inaccuracy
<20ms
Reset ratio
0.95
Trip logic (94)
Impulse time duration accuracy
<3ms
7.3
C
ONTROL FUNCTIONS
Synchrocheck function du/df (25)
Rated Voltage Un
100/200V, setting parameter
Voltage effective range
10-110 % of Un
Voltage inaccuracy
±
1% of Un
Frequency effective range
47.5
–
52.5 Hz
Frequency inaccuracy
±
10mHz
Phase angle inaccuracy
±
3
°
Operate time inaccuracy
±
3ms
Reset time
<50ms
Reset ratio
0.95
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...