Instruction manual
–
AQ F3x0 Feeder protection IED
111 (162
)
Table 3-59 Setting parameters of the synchro check / synchro switch function
Parameter
Setting value, range
and step
Description
Voltage select
L1-N
L2-N
L3-N
L1-L2
L2-L3
L3-L1
Reference voltage selection. The function will monitor the
selected voltage for magnitude, frequency and angle
differences. Default setting is L1-N
U Live
60
…
110 % by step of
1 %
Voltage setting limit for
“
Live Line
”
detection. When measured
voltage is above the setting value the line is considered
“
Live
”
.
Default setting is 70 %.
U Dead
10
…
60 % by step of
1%
Voltage setting limit for
“
Dead Line
”
detection. When measured
voltage is below the setting value the line is considered
“
dead
”
.
Default setting is 30 %.
Breaker Time
0
…
500 ms by step of
1 ms
Breaker operating time at closing. This parameter is used for
the synchro switch closing command compensation and it
describes the breaker travel time from open position to closed
position from the close command. Default setting is 80 ms.
Close Pulse
10
…
60000 ms by
step of 1 ms
Close command pulse length. This setting defines the duration
of close command from the IED to the circuit breaker. Default
setting is 1000 ms.
Max
Switch
Time
100
…
60000 ms by
step of 1 ms
Maximum allowed switching time. In case synchro check
conditions are not fulfilled and the rotation of the networks is
slow this parameter defines the maximum waiting time after
which the close command is failed. Default setting is 2000ms.
Operation Auto On
Off
ByPass
Operation mode for automatic switching. Selection can be
automatic switching off, on or bypassed. If the Operation Auto
is set to
“
Off
”
automatic switch checking is disabled. If selection
is
“
ByPass
”
Automatic switching is enabled with bypassing the
bus and line energization status checking. When the selection
is
“
On
”
also the energization status of bus and line are checked
before processing the command. Default setting is
“
On
”
SynSW Auto
On
Off
Automatic synchroswitching selection. Selection may be
enabled
“
On
”
or disabled
“
Off
”
. Default setting is Enabled
“
On
”
.
Energizing
Auto
Off
DeadBus LiveLine
LiveBus DeadLine
Any energ case
Energizing mode of automatic synchroswitching. Selections
consist of the monitoring of the energization status of the bus
and line. If the operation is wanted to be LiveBus LiveLine or
DeadBus DeadLine the selection is
“
Any energ case
”
. Default
setting is DeadBus LiveLine.
Udiff SynChk
Auto
5
…
30 % by step of 1
%
Voltage difference checking of the automatic synchrocheck
mode. If the measured voltage difference is below this setting
the condition applies. Default setting is 10 %.
Udiff SynSW
Auto
5
…
30 % by step of 1
%
Voltage difference checking of the automatic synchroswitch
mode. If the measured voltage difference is below this setting
the condition applies. Default setting is 10 %.
MaxPhasediff
Auto
5
…
80 deg by step of
1 deg
Phase difference checking of the automatic synchroswitch
mode. If the measured phase difference is below this setting the
condition applies. Default setting is 20 deg.
FrDiff SynChk
Auto
0.02
…
0.50 Hz by
step of 0.01 Hz
Frequency difference checking of the automatic synchrocheck
mode. If the measured phase difference is below this setting the
condition applies. Default setting is 0.02 Hz.
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...