Instruction manual
–
AQ F3x0 Feeder protection IED
68 (162
)
Table 3-29: Setting parameters of the CBFP function
Parameter
Setting value, range
and step
Description
Operation
Off
Current
Contact
Current/Contact
Operating mode selection for the function. Operation can be
either disabled “Off” or monitoring either measured current or
contact status or both current and contact status. Default
setting is “Current”.
Start current
Ph
20…200 % by step of
1 %
Pick-up current for the phase current monitoring. Default
setting is 30 %.
Start current
N
10…200 % by step of
1 %
Pick-up current for the residual current monitoring. Default
setting is 30 %
Backup Time
Delay
60…1000 ms by step
of 1 ms
Time delay for CBFP tripping command for the back-up
breakers from the pick-up of the CBFP function monitoring.
Default setting is 200 ms.
Pulse length
0…60000 ms by step
of 1 ms
CBFP pulse length setting. Default setting is 100 ms.
3.2.16
I
NRUSH CURRENT DETECTION
(INR2),
(68)
The current can be high during transformer energizing due to the current distortion caused by
the transformer iron core asymmetrical saturation. In this case, the second harmonic content
of the current is applied to disable the operation of the desired protection function(s).
The inrush current detection function block analyses the second harmonic content of the
current, related to the fundamental harmonic. If the content is high, then the assigned status
signal is set to “true” value. If the duration of the active status is at least 25 ms, then the
resetting of the status signal is delayed by an additional 15 ms. Inrush current detection is
applied to residual current measurement also with dedicated separate function.
Table 3-30: Setting parameters of the inrush function
Parameter
Setting value, range
and step
Description
Operation
Off
Current
Contact
Current/Contact
Operating mode selection for the function. Operation can be
either disabled “Off” or monitoring either measured current o
r
contact status or both current and contact status. Default
setting is “Current”.
Start current
Ph
20…200 % by step of
1 %
Pick-up current for the phase current monitoring. Default
setting is 30 %.
Start current
N
10…200 % by step of
1 %
Pick-up current for the residual current monitoring. Default
setting is 30 %
Backup Time
Delay
60…1000 ms by step
of 1 ms
Time delay for CBFP tripping command for the back-up
breakers from the pick-up of the CBFP function monitoring.
Default setting is 200 ms.
Pulse length
0…60000 ms by step
of 1 ms
CBFP pulse length setting. Default setting is 100 ms.
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...