Table 3-31 Impedance calculation formulas
The central column of table contains the formula for calculation. The formulas referred to in
the right-hand-side column yield the same impedance value.
Equation 3-4 Earth fault compensation factor
Equation presents the earth fault compensation factor.
Table above shows that the formula containing the complex earth fault compensation factor
yields the correct impedance value in case of phase-to-earth faults only; the other formula
can be applied in case of phase-to-phase faults without ground. In case of other kinds of
faults (three-phase (-to-earth), phase-to-phase-to-earth) both formulas give the correct
impedance value if the appropriate voltages and currents are applied.