![Arcteq AQ F3 0 Series Скачать руководство пользователя страница 158](http://html1.mh-extra.com/html/arcteq/aq-f3-0-series/aq-f3-0-series_instruction-manual_2964933158.webp)
Instruction manual
–
AQ F3x0 Feeder protection IED
158 (162
)
7.4.2
V
OLTAGE MEASUREMENT MODULE
Rated voltage Un
100/√3, 100V, 200/√3, 200V
(parameter settable)
Number of channels per module
4
Rated frequency
50Hz
60Hz (ordering option)
Burden
<1VA at 200V
Voltage withstand
250V (continuous)
275VAC/350VDC (1s)
Voltage measurement range
0.05-1.2xUn
Power consumption
0.61VA at 200V
0.2 VA at 100V
Relative accuracy
±0.5
% (>0.6Un)
Frequency measurement range
±0.01 % at Ux ≥ 25% of rated
voltage
Phase angle accuracy
≤ 0.5 º at Ux ≥ 25% of rated
voltage
7.4.3
H
IGH SPEED TRIP MODULE
Rated voltage Un
110/220VDC
Max. withstand voltage
242V DC
Number of outputs per module
4
Continuous carry
8A
Making capacity
30A (0.5s)
Breaking capacity
4A (L/R=40ms, 220Vdc)
7.4.4
B
INARY OUTPUT MODULE
Rated voltage Un
250Vac/dc
Number of outputs per module
7 (NO) + 1(NC)
Continuous carry
8A
Breaking capacity
0.2A (L/R=40ms, 220Vdc)
7.4.5
B
INARY INPUT MODULE
Rated voltage Un
110 or 220Vdc (ordering option)
Number of inputs per module
12 (in groups of 3) or 16 (in
groups of 8)
Current drain
approx. 2mA per channel
Breaking capacity
0.2A (L/R=40ms, 220Vdc)
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...