6.5
B
INARY OUTPUT MODULES FOR SIGNALING
The signaling output modules can be ordered as 8 relay outputs with dry contacts.
•
Rated voltage: 250 V AC/DC
•
Continuous carry: 8 A
•
Breaking capacity, (L/R=40ms) at 220 V DC: 0,2 A
•
8 contacts, 7 NO and 1 NC
No. Name
1 BOut_H01 Common
2 BOut_H01 NO
3 BOut_H02 Common
4 BOut_H02 NO
5 BOut_H03 Common
6 BOut_H03 NO
7 BOut_H04 Common
8 BOut_H04 NO
9 BOut_H05 Common
10 BOut_H05 NO
11 BOut_H06 Common
12 BOut_H06 NC
13 BOut_H07 Common
14 BOut_H07 NO
15 BOut_H08 Common
16 BOut_H08 NC
"H" R8+/80