Instruction manual
–
AQ F3x0 Feeder protection IED
28 (162
)
Parameter
Setting value, range
and step
Description
Operation
Off
Peak value
Fundamental value
Operating mode selection of the function. Can be disabled,
operating based into measured current peak values or
operating based into calculated current fundamental
frequency RMS values. Default setting is “Peak value”
.
Start current
10…400 %, by step
of 1%
Pick-up setting of the function. Setting range is from 10 % to
400 % of the configured nominal secondary current. Setting
step is 1 %. Default setting is 200 %.