The breaker failure protection function resets only if all conditions for faultless state are
fulfilled. If at the end of the running time of the backup timer the currents do not drop below
the pre-defined level, and/or the monitored circuit breaker is still in closed position, then a
backup trip command is generated in the phase(s) where the timer(s) run off.
The time delay is defined using the parameter “Backup Time Delay”. If repeated trip command
is to be generated for the circuit breakers that are expected to open, then the enumerated
parameter “Retrip” must be set to “On”. In this case, at the end of the timer(s) the delay of
which is set by the timer p
arameter “Retrip Time Delay”, a repeated trip command is also
generated. The pulse duration of the trip command is shall the time defined by setting the
parameter “Pulse length”. The breaker failure protection function can be enabled or disabled
by setting
the parameter “Operation” to “Off”.
Dynamic blocking is possible using the binary input “Block”. The co
nditions can be
programmed by the user.
Figure 3-38: Operation logic of the CBFP function
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...