![Arcteq AQ F3 0 Series Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/arcteq/aq-f3-0-series/aq-f3-0-series_instruction-manual_2964933051.webp)
Instruction manual
–
AQ F3x0 Feeder protection IED
51 (162
)
Operating time of the function can be definite time or IDMT based on user selection. Operating
characteristics of the IDMT function are presented in the chapter 3.1.2 Three-phase time
overcurrent protection I>, I>> (50/51).
Table 3-19: Setting parameters of the directional overcurrent function
Parameter
Setting value, range
and step
Description
Direction
NonDir
Forward
Backward
Direction mode selection. Operation can be non directional,
forward direction or backward direction. Default setting is
“Forward”.
Operating
angle
30…90 deg with step
of 1 deg
Operating angle setting. Defines the width of the operating
characteristics in both sides of the characteristic angle.
Default setting is 60 deg which means that the total width of
the operating angle is 120 deg.
Characteristic
angle
40…90 deg with step
of 1 deg
Characteristic angle setting. Defines the center angle of the
characteristics. Default setting is 60 deg.
Operation
Off
DefinitTime
IEC Inv
IEC VeryInv
IEC ExtInv
IEC LongInv
ANSI Inv
ANSI ModInv
ANSI VeryInv
ANSI ExtInv
ANSI LongInv
ANSI LongVeryInv
ANSI LongExtInv
Operating mode selection of the function. Can be disabled,
Definite time or IDMT operation based into IEC or ANSI/IEEE
standards. Default setting is
“DefinitTime”
Start current
5
…1000 %, by step
of 1%. Default 50 %
Pick-up current setting of the function. Setting range is from
5% of nominal current to 1000% with step of 1 %. Default
setting is 50 % of nominal current.
Min Delay
0…60000 ms, by step
of 1 ms. Default 100
ms
Minimum operating delay setting for the IDMT characteristics.
Additional delay setting is from 0 ms to 60000 ms with step of
1 ms. Default setting is 100 ms.
Definite delay
time
0…60000 ms by step
of 1 ms. Default 100
ms
Definite time operating delay setting. Setting range is from 0
ms to 60000 ms with step of 1 ms. Default setting is 100 ms.
This parameter is not in use when IDMT characteristics is
selected for the operation.
Reset delay
0…60000
ms by step
of 1 ms. Default 100
ms
Settable reset delay for definite time function and IEC IDMT
operating characteristics. Setting range is from 0 ms to 60000
ms with step of 1 ms. Default setting is 100 ms. This
parameter is in use with definite time and IDMT
characteristics.
Time Mult
0.
05…999.00 by step
of 0.01. Default 1.00
Time multiplier / time dial setting of the IDMT operating
characteristics. Setting range is from 0.05 to 999.00 with step
of 0.01. This parameter is not in use with definite time
characteristics.
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...