Instruction manual
–
AQ F3x0 Feeder protection IED
88 (162
)
Table 3-40 Calculated analogue values of the distance protection function.
Measured value
Dim.
Explanation
ZL1 = RL1+j XL1
ohm
Measured positive sequence impedance in the L1N loop,
using the zero sequence current compensation factor for
zone 1
ZL2 = RL2+j XL2
ohm
Measured positive sequence impedance in the L2N loop,
using the zero sequence current compensation factor for
zone 1
ZL3 = RL3+j XL3
ohm
Measured positive sequence impedance in the L3N loop,
using the zero sequence current compensation factor for
zone 1
ZL1L2 = RL1L2+j XL1L2 ohm
Measured positive sequence impedance in the L1L2 loop
ZL2L3 = RL2L3+j XL2L3 ohm
Measured positive sequence impedance in the L2L3 loop
ZL3L1 = RL3L1+j XL3L1 ohm
Measured positive sequence impedance in the L3L1 loop
Fault location
km
Measured distance to fault
Fault react.
ohm
Measured impedance in the fault loop
The symbol of the function block in the AQtivate 300 software
Figure 3-48: The function block of the distance protection function with polygon
characteristic
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...