Voltage interruption, when the RMS value of the measured voltage is below a minimum
level specified by a parameter. For the evaluation, the duration of the voltage interruption
should be between a minimum and a maximum time value defined by parameters.
Figure 3-5 Voltage interruption
Sag and swell detection
Voltage sag is detected if any of the three phase-to-phase voltages falls to a value between
the “Sag limit” setting and the “Interruption Limit” setti
ng. In this state, the binary output
“Sag” signal is activated. The signal resets if all of the three phase
-to-phase voltages rise
above the “Sag limit”, or if the set time “Maximum duration” elapses. If the voltage returns
to normal state after the set “M
i
nimum duration” and before the time “Maximum duration”
elapses, then the “Sag Counter” increments by 1, indicating a short
-time voltage variation.
The report generated includes the duration and the minimum value. A voltage swell is
detected if any of the three phase-to-
phase voltages increases to a value above the “Swell
limit” setting. In this state, the binary output “Swell” signal is activated. The signal resets if
all of the three phase-to-
phase voltages fall below the “Swell limit”, or if the set tim
e
“Maximum duration” elapses. If the voltage returns to normal state after the “Minimum
duration” and before the time “Maximum duration” elapses, then the “Swell Counter”
increments by 1, indicating a short-time voltage variation.
The report generated includes the duration and the maximum value. A voltage interruption
is detected if all three phase-to-
phase voltages fall to a value below the “Interruption Limit”
setting. In this state, the binary output “Interruption” is activated. The signal resets if any
of
the three phase-to-
phase voltages rises above the “Interruption limit”, or if the time
“Maximum duration” elapses. No counter is assigned to this state.
The inputs of the sag and swell detection function are:
•
RMS values of the of three phase-to-phase voltages,
•
Binary input
•
Setting parameters
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...