![Arcteq AQ F3 0 Series Скачать руководство пользователя страница 130](http://html1.mh-extra.com/html/arcteq/aq-f3-0-series/aq-f3-0-series_instruction-manual_2964933130.webp)
Instruction manual
–
AQ F3x0 Feeder protection IED
130 (162
)
Operation counter
Operation counter
DC OPCap
3.3.12
M
EASURED VALUES
The measured values can be checked on the touch-scr
een of the device in the “On
-line
functions” page, or us
ing an Internet browser of a connected computer. The displayed
values are secondary voltages and currents, except the block “Line measurement”. This
specific block displays the measured values in primary units, using the VT and CT primary
value settings.
Table 3-70 Analogue value measurements
Analog value
Explanation
VT4 module
Voltage Ch - U1
RMS value of the Fourier fundamental harmonic voltage component in phase
L1
Angle Ch - U1
Phase angle of the Fourier fundamental harmonic voltage component in phase
L1*
Voltage Ch - U2
RMS value of the Fourier fundamental harmonic voltage component in phase
L2
Angle Ch - U2
Phase angle of the Fourier fundamental harmonic voltage component in phase
L2*
Voltage Ch - U3
RMS value of the Fourier fundamental harmonic voltage component in phase
L3
Angle Ch - U3
Phase angle of the Fourier fundamental harmonic voltage component in phase
L3*
Voltage Ch - U4
RMS value of the Fourier fundamental harmonic voltage component in
Channel U4
Angle Ch - U4
Phase angle of the Fourier fundamental harmonic voltage component in
Channel U4*
CT4 module
Current Ch - I1
RMS value of the Fourier fundamental harmonic current component in phase
L1
Angle Ch - I1
Phase angle of the Fourier fundamental harmonic current component in phase
L1*
Current Ch - I2
RMS value of the Fourier fundamental harmonic current component in phase
L2
Angle Ch - I2
Phase angle of the Fourier fundamental harmonic current component in phase
L2*
Current Ch - I3
RMS value of the Fourier fundamental harmonic current component in phase
L3
Angle Ch - I3
Phase angle of the Fourier fundamental harmonic current component in phase
L3*
Current Ch - I4
RMS value of the Fourier fundamental harmonic current component in Channel
I4
Angle Ch - I4
Phase angle of the Fourier fundamental harmonic current component in
Channel I4*
Values for the directional measurement
L12 loop R
Resistance of loop L1L2
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...