VIN 0-10V
IIN 4-20mA
A102
A102
14. IIN 4-20mA
When this option is selected, the set frequency
M105
corresponds to analog input IIN. The output
frequency will be minimum at 4 mA and maximum at 20 mA.
15. PLC A-O/P 1
When this option is selected, the set frequency
M105
corresponds to PLC A-O/P 1. This Parameter
option value can be set directly from In-built PLC function. The output frequency will be minimum at
0d and maximum at 1000d.
16. PLC A-O/P 2
When this option is selected, the set frequency
M105
corresponds to PLC A-O/P 2. This Parameter
option value can be set directly from In-built PLC function. The output frequency will be minimum at
0d and maximum at 1000d.
17. PLC A-O/P 3
When this option is selected, the set frequency
M105
corresponds to PLC A-O/P 3. This Parameter
option value can be set directly from In-built PLC function. The output frequency will be minimum at
0d and maximum at 1000d.
18. PLC A-O/P 4
When this option is selected, the set frequency
M105
corresponds to PLC A-O/P 4. This Parameter
option value can be set directly from In-built PLC function. The output frequency will be minimum at
0d and maximum at 1000d.
For In-built PLC function and related parameters detail, refer Mode-P.
A107: Local Torque Setting (%)
This parameter is available only if motor control mode
A401 = 3, 4, 7, 8
are selected. This setting
value is used as the torque command value when torque reference input is
Local
(A108 = 1)
.
A108: Torque Reference Input
This parameter can be used for torque reference input to the AC DRIVE. The torque reference can be
independently selected from the given options even if the AC DRIVE is controlled from local (Digital
Operation Panel), terminal or serial. The different torque reference inputs are explained as under. The
minimum limit is 0% and maximum limit is 200%, if output current does not exceed
B301
value.
1. Local
When this option is selected, the set torque
M107
corresponds to local set torque
A107
. Use digital
operation panel (keypad) to change the set value. The monitor mode parameter
M107
shows the
Содержание Axpert-Eazy AMT-011-4
Страница 2: ...Amtech ii...
Страница 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Страница 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Страница 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Страница 38: ...Amtech 4 10 4 This page is intentionally left blank...
Страница 46: ...Amtech 5 8 5 This page is intentionally left blank...
Страница 216: ...Amtech 13 6 13 This page is intentionally left blank...
Страница 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Страница 239: ...Notes...
Страница 240: ...Notes...
Страница 241: ......
Страница 242: ...AMTECH...