Axpert-Eazy
AC Variable Frequency Drive
8.1
8
CHAPTER-8: MAINTENANCE, INSPECTION AND PART REPLACEMENT
DANGER
Always wait at least 20 minutes after turning the input power OFF before starting inspection.
Wait at least 20 minutes after turning the input power OFF before starting work. Make sure that
the displays on the operation panel have gone out before removing the front cover.
Remove the front cover, and confirm that the “DC BUS CHARGE LED” on bleeder board has
gone out. Also check that the voltage between terminals L+1 or L+2 and L– is 15V or less before
starting the inspections.
Failure to observe this could lead to electric shocks.
Maintenance, inspections and part replacement must be done by a designated person.
(Remove all metal accessories such as watches, bracelets, etc., before starting the work.)
(Always use an insulation measure tool.)
Failure to observe this could lead to electric shocks and injuries.
Always turn the power OFF before inspecting the motor or machine. A potential is applied on the
motor terminal even when the motor is stopped.
Failure to do so could lead to electric shocks and injuries.
Do not use parts other than those designated for the replacement parts.
Contact your AC DRIVE dealer for replacement parts.
Failure to observe this could lead to fires.
Never modify the product.
Failure to observe this could lead to electric shocks or injuries or product failure.
CAUTION
Vacuum the AC DRIVE with a vacuum cleaner to clean it. Do not use water or organic solvents.
Failure to observe this could lead to fires or damage.
Do not megger the unit.
Failure to observe this could lead to damage to semiconductor devices.
8-1 Inspection items
The inspections must be carried out periodically according to the working environment and frequency
of use. If there are any abnormalities, the cause must be inspected immediately and countermeasures
taken.
8-1-1 Daily inspections
Inspection item
Inspection details and work
Temperature/humidity Confirm that the ambient temperature is 0°C (32°F) to 50°C (122°F) for 400
Volt series Drive and 0°C (32°F) to 40°C (104°F) for 500/600 Volt series Drive,
and that the humidity is 95% or less with no dew condensation.
Oil mist and dust
Confirm that there is no oil mist or dust in the AC DRIVE.
Abnormal noise and
vibration
Confirm that there is no abnormal noise or vibration from the installation site or
AC DRIVE.
Input power source
Confirm that the input voltage and frequency are within the specifications
range.
Cooling fan
Confirm that the cooling fan rotates normally and that no lint, etc. is stuck on it.
Indicator
Confirm that all lamps on the operation panel light properly.
Содержание Axpert-Eazy AMT-011-4
Страница 2: ...Amtech ii...
Страница 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Страница 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Страница 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Страница 38: ...Amtech 4 10 4 This page is intentionally left blank...
Страница 46: ...Amtech 5 8 5 This page is intentionally left blank...
Страница 216: ...Amtech 13 6 13 This page is intentionally left blank...
Страница 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Страница 239: ...Notes...
Страница 240: ...Notes...
Страница 241: ......
Страница 242: ...AMTECH...