Axpert-Eazy
AC Variable Frequency Drive
6-45
6
M G 8 * D E F A U L T
D I F F E R * *
A 1 0 1
L o c a l
S e t
F r e q
2 0 . 0 0
H z
F w d , L c l
, N o r m a l
R u n
MODE – A
GROUP – 1: FREQUENCY SETTING
A101: Local Set Frequency (Hz)
This is the set frequency when the frequency reference input source is
Local
(
A106
=1)
. The output
will ramp to this frequency, when start command is given.
The minimum limit for this parameter is decided by minimum frequency
A102
. If
A102
is set higher
then
A101
, the value of
A102
is automatically assigned to
A101
.
The maximum value of this parameter is decided by Maximum frequency
A103
. The value of
A101
cannot be set higher than
A103
.
A102: Minimum Frequency (Hz)
This is the minimum output frequency of the AC DRIVE.
In terminal mode, this is the minimum output attained with minimum analog input reference. This
value should always be lower then the maximum frequency
A103
. The minimum frequency
will be
reached after start command with selected acceleration ramp up time. This is applicable to all
frequency references including jog select input, preset inputs and static pot inputs.
A103: Maximum Frequency (Hz)
This is the maximum output frequency of the AC DRIVE.
In terminal mode, this is the maximum output attained with maximum analog input reference.
A104: Jog Frequency (Hz)
This frequency setting is selected when executing jogging run with the programmable sequence input
command
Jog Select
. The selected acceleration time
A201
(or
A203
) / deceleration time
A202
(or
A204
) and stop mode
A304
will be applicable to this signal.
If auxiliary drive is selected, then the acceleration time
D206
(or
A203)
/ deceleration time
D207 (
or
A204)
will be applicable.
The minimum limit for this parameter is
A102
and maximum limit is
A103
.
Speed search function is carried out, when executing jogging run command, if it is enabled.
Jog
Select
is valid in all conditions of
A301.
However,
RUN
command has the higher priority then
Jog
Select
, if both the signals are input together.
A105: Line Speed Setting
The entered value will be displayed as motor speed in
M102
at 50 Hz, if motor control mode
A401=1
(open loop v/f mode). It will not have any effect in other modes.
The final speed of the driven load can be displayed by this parameter. The value to be entered can be
derived at with following formula:
Содержание Axpert-Eazy AMT-011-4
Страница 2: ...Amtech ii...
Страница 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Страница 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Страница 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Страница 38: ...Amtech 4 10 4 This page is intentionally left blank...
Страница 46: ...Amtech 5 8 5 This page is intentionally left blank...
Страница 216: ...Amtech 13 6 13 This page is intentionally left blank...
Страница 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Страница 239: ...Notes...
Страница 240: ...Notes...
Страница 241: ......
Страница 242: ...AMTECH...