6-128
6
Input from Display Panel into P101 to PA01
Parameter No.
PLC Command
Description
P101
047001001000
Copy the PSI1 status into Flag no. 1.
P102
047002002000
Copy the PSI2 status into Flag no. 2.
P103
008003001000
Copy the bit status Flag no. 1 into Flag no. 3.
P104
008004002000
Copy the bit status Flag no. 2 into Flag no. 4.
P105
019001001002
AND operation between two Flags and result will be stored in flag
no. 1.
P106
022003003001
XOR operation between two Flags and result will be stored in flag
no. 3.
P107
022004004001
XOR operation between two Flags and result will be stored in flag
no. 4.
P108
048012001000
Write the Flag no.1’s result into the PSI's selectable option no. 12
which is
Ext Flt (NO)
.
P109
048024003000
Write the Flag no. 3’s result into the PSI's selectable option no. 24,
which is
RUN
.
P110
048002004000
Write the Flag no. 4’s result into the PSI's selectable option no. 2,
which is
Jog Select
.
P201
000000000000
End of Program.
Note:
User can use 0 to 99 single bit locations for general application.
User has to set following parameter.
1. Enable PLC function from C312.
2. Select option 28 in C101.
3. Select option 29 in C102.
4.
Select option 1 in C114.
Example 2
This application can be used when RUN is required after certain delay.
In this example when Digital input will be applied to PSI1, RUN will be activated after 5
seconds of delay. To keep RUN status active PSI1 should be applied permanently otherwise
RUN will become Inactive.
PSI1
RUN
Program Code:
Input from Display Panel into P101 to PA01.
Parameter No.
PLC Command
Description
P101
047001001000
Copy the PSI1 status into Flag no. 1.
P102
008092001000
Copy the bit status of Flag no. 1 into Flag no. 92.
P103
057000000000
Here 5000 count (C701*C702) has been loaded to the TIMER1.
P104
048024093000
Write the bit status of Flag to the PSI's selectable option number
24, which is RUN.
P105
000000000000
End of Program.
Note:
User should consider fix format for TIMER COMMAND. There are 4 Timer commands. All are used as
same format.
Timer of 5
Seconds
Содержание Axpert-Eazy AMT-011-4
Страница 2: ...Amtech ii...
Страница 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Страница 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Страница 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Страница 38: ...Amtech 4 10 4 This page is intentionally left blank...
Страница 46: ...Amtech 5 8 5 This page is intentionally left blank...
Страница 216: ...Amtech 13 6 13 This page is intentionally left blank...
Страница 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Страница 239: ...Notes...
Страница 240: ...Notes...
Страница 241: ......
Страница 242: ...AMTECH...