Axpert-Eazy
AC Variable Frequency Drive
6-25
6
No.
Parameter
Unit
Def
Min
Max
Res
Description
WP
D305 DC Brake Time
Sec
0.0
0.0
25.0
0.1
It is amount of time that DC braking will be
applied when stop command is issued. To
disable DC Braking operation set this parameter
to zero.
GROUP-4: LIMITING PARAMETER
D401 Stall Current Limit
%
125.0
0.0
200.0
0.1
Set the current value as a percentage of motor
rated current for normal running condition.
The default value is 155%, when heavy duty is
set.
D402 Adjustable Over
Current Level
%
300
50
300
1
Set the upper current limit as a percentage of
motor rated current for running condition. When
set to 300%, this feature is disabled.
D403 Acceleration
Current Limit
%
150
50
200
1
Set the upper current limit as a percentage of
motor rated current for Acceleration.
D404 Under Current
Level
%
0
0
90
1
Set the lower current limit as a percentage of
motor rated current for running condition.
Содержание Axpert-Eazy AMT-011-4
Страница 2: ...Amtech ii...
Страница 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Страница 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Страница 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Страница 38: ...Amtech 4 10 4 This page is intentionally left blank...
Страница 46: ...Amtech 5 8 5 This page is intentionally left blank...
Страница 216: ...Amtech 13 6 13 This page is intentionally left blank...
Страница 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Страница 239: ...Notes...
Страница 240: ...Notes...
Страница 241: ......
Страница 242: ...AMTECH...