Amtech
11.14
10
11
2
03h
Indication of read operation
3
14h
Total 20 data bytes packed after byte 3.
4-23
20 Bytes
Data Bytes are in the ascending orders of parameter number. First two
for 40001, next two for 40002 and so on.
24
CRC Low
CRC Low Byte
25
CRC High
CRC High Byte. The High and Low bytes are reversed in CRC
transmission. The method of calculating CRC is described in the next
section.
5.3 Write Single Parameter
This query is used for single parameter read. Total 8 bytes are transmitted. 3.5-character times delay
is provided at the start and end of the query for indication of starting and ending of query
For example if you want to write parameter 40096 then the format of query is as below. The range of
this parameter is 0.0 to 100.0. If the sending value is 40.0 then the transmitted value in query is 40.0 *
10 = 400 because this parameter has resolution of 1 digit after decimal. After converting to
hexadecimal it becomes 190h.
Byte
Number
Query Bytes Description
1
01h
First byte is the address of the modbus slave device referred as station
number.
2
06h
Indication of single write operation
3
00h
Starting address High byte
4
5Fh
Starting Address Low byte. Parameter 40096 is addressed as 005Fh.
Byte 3 and 4 has right justified packed value of parameter number.
5
01h
Data High Byte
6
90h
Data Low Byte.
7
CRC Low
CRC Low Byte
8
CRC High
CRC High Byte. The High and Low bytes are reversed in CRC
transmission. The method of calculating CRC is described in the next
section.
If the query is received properly then the response is the echo of the query after the value is being set.
5.4 Write Multiple Parameter
This query is used for multiple parameters Write. 3.5-character times delay is provided at the start and
end of the query for indication of starting and ending of query.
For example if you want to read parameter 40084 to 40093 then the format of query is as below. Then
total 29 bytes transmitted.
Byte
Number
Query Bytes Description
1
01h
First byte is the address of the modbus slave device referred as station
number.
2
10h
Indication of multiple write operation
3
00h
Starting address High byte
4
53h
Starting Address Low byte. Parameter 40084 is addressed as 0053h.
Содержание Axpert-Eazy AMT-011-4
Страница 2: ...Amtech ii...
Страница 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Страница 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Страница 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Страница 38: ...Amtech 4 10 4 This page is intentionally left blank...
Страница 46: ...Amtech 5 8 5 This page is intentionally left blank...
Страница 216: ...Amtech 13 6 13 This page is intentionally left blank...
Страница 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Страница 239: ...Notes...
Страница 240: ...Notes...
Страница 241: ......
Страница 242: ...AMTECH...