Axpert-Eazy
AC Variable Frequency Drive
6-129
6
Example,
057000000000
057 is opcode for TIMER1 command.
Parameter C701 = 1
Parameter C702 = 5000
So, 1 * 5000 = 5000 count will be loaded in to timer1 (1 count = 1ms)
User has to set following parameter.
1. Enable PLC function from C312.
2 Select 28 no. Selectable option in C101.
3. C701 = 1 and C702 = 5000.
4. Select option 1 (Not Used) in C114.
Example 3
This example demonstrates how to use memory location (Register 0 to 114) for 16-bit value.
Program Code:
Input from Display Panel into P101 to PA01.
Parameter No.
PLC Command
Description
P101
001002000050
Load 16-bit Immediate value (50) into Register no.2
P102
054001002000
Content of Register no. 2 is copied to PLC A-O/P 1. Here 0d = 0
volt and 1000d = 10 volt
P103
001003000010
Load 16-bit Immediate value into Register no.3
P104
035001003002
It will compare two Registers. If Register 3 is greater then 2, than
flag no. 1 will be SET (1) otherwise it will reset (0).
P105
049002001000
Write the bit status of Flag no.1 into PLCPSO2.
P106
000000000000
End of Program.
Note:
User should consider fix format for
REG_LD
COMMAND.
Example,
001002000050
001 is opcode for REG_LD
command.
002 Register number 2(Memory location for 16-bit value.)
000050 indicate one signed 16-bit value. (Maximum value is 32767.)
User has to set following parameter.
1. Enable PLC function from C312.
2. Select 8 no. Selectable option in C201. Output will come on Vo-1 terminal.
3. Selects 27 no. Selectable option in C107. Output will come on PSO1 terminal.
Note:
User can use 0 to 85 16-bit memory locations for general application. These are read and write memory
locations. From 86 to 114 memory location contains analog values of internal parameters, which are given in In-
built PLC Function’s manual. These memory locations are read only.0 to 114 16-bit memory locations and 0 to 99
bit memory locations both are different.
Содержание Axpert-Eazy AMT-011-4
Страница 2: ...Amtech ii...
Страница 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Страница 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Страница 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Страница 38: ...Amtech 4 10 4 This page is intentionally left blank...
Страница 46: ...Amtech 5 8 5 This page is intentionally left blank...
Страница 216: ...Amtech 13 6 13 This page is intentionally left blank...
Страница 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Страница 239: ...Notes...
Страница 240: ...Notes...
Страница 241: ......
Страница 242: ...AMTECH...