No.
Parameter
Unit
Def
Min
Max
Res.
Description
WP
A202 Deceleration Time-
1
Sec
20.0
0.1
6000.0
0.1
Time needed to change the output frequency
from maximum to zero.
A203 Acceleration Time-
2
Sec
10.0
0.1
6000.0
0.1
The acceleration time and deceleration time for
the second ramp function.
A204 Deceleration Time-
2
Sec
20.0
0.1
6000.0
0.1
A205 S-Curve Selection
0
0
1
1
This will enable the s-curve shape during
acceleration /deceleration.
=0: Disable
=1: Enable
A206 S-Curve Time-1
Sec
0.1
0.1
3000.0
0.1
The maximum value will depend on the
currently selected ramp time.
A207 S-Curve Time-2
Sec
0.1
0.1
3000.0
0.1
The maximum value will depend on the
currently selected ramp time.
A208 Current Limit
Acceleration Time
Sec
10.0
0.5
6000.0
0.1
This is ramp up time during the stall current
limit.
A209 Current Limit
Deceleration Time
Sec
5.0
0.5
6000.0
0.1
This is ramp down time during the stall current
limit.
A210 Acceleration
Deceleration
Multiplier
1
1
3
1
This is multiplier for the acceleration/
deceleration time related parameters
A201~A207 and D206~D207.
=1: x1
=2: x10
=3: x100
GROUP-3: START / STOP SELECTION & DC BRAKING
A301 Start Control
1
1
3
1
Select start location.
=1: Local
=2: Terminal
=3: Serial
A302 Maintained Start /
Stop
0
0
1
0
When using terminal start/ stop facility, this
parameter gives the choice of having
maintained or momentary contacts for start or
stop.
=0: The start control maintained type
=1: The start/ stop control momentary type.
A303 Start Delay Time
Sec
0.0
0.0
10.0
0.1
The motor will be delayed from the run
command by the set time. This is used for
synchronization with peripheral machines such
as mechanical brakes.
A304 Stop Mode
0
0
1
1
Select the stop method.
=0: Ramp down to stop
=1: Coast to stop
A305 Motor Direction
0
0
1
1
Select direction of motor rotation.
=0: Forward
=1: Reverse
A306 DC Brake Start
Frequency
Hz
1.50
0.00
50.00
0.01 It is a frequency at which DC braking is initiated
during stop.
A307 DC Brake Current
%
50
15
150
1
Configure amount of current available for the
DC braking when DC braking is used during
stop.
A308 DC Brake Time
Sec
0.0
0.0
25.0
0.1
It is amount of time that DC braking will be
applied when stop command issued. To disable
DC Braking operation set this parameter to
zero.
Содержание Axpert-Eazy AMT-011-4
Страница 2: ...Amtech ii...
Страница 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Страница 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Страница 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Страница 38: ...Amtech 4 10 4 This page is intentionally left blank...
Страница 46: ...Amtech 5 8 5 This page is intentionally left blank...
Страница 216: ...Amtech 13 6 13 This page is intentionally left blank...
Страница 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Страница 239: ...Notes...
Страница 240: ...Notes...
Страница 241: ......
Страница 242: ...AMTECH...