Amtech
6-22
6
No.
Parameter
Unit
Def
Min
Max
Res
Description
WP
C614
PID Display Unit
Selection
1
0
69
1
Select the unit for the PID signal.
=0: No Unit
=3: kg/cm
2
=6: CFM
=9: Amp
=12: Hz
=15: rpm
=18: mA
=21: kWh
=24: m/s
=27: kPa
=30: MGD
=33: kb/s
=36: ppm
=39: Km
3
/h
=42: m
3
/min
=45: kg/h
=48: GPS
=51: gal/h
=54: ft
3
/h
=57: lb/h
=60: inH
2
O
=63: lbsi
=66: d
=69: Nm
=1: %
=4: ºC
=7: m
3
/h
=10: kW
=13: s
=16: kh
=19: mV
=22: hp
=25: dm
3
/s
=28: GPM
=31: inHg
=34: kHz
=37: pps
=40: l/h
=43: kg/s
=46: mbar
=49: gal/s
=52: ft
3
/s
=55: lb/s
=58: FPS
=61: in wg
=64: ms
=67: inWC
=2: PSI
=5: ºF
=8: LPM
=11: V
=14: h
=17: lb ft
=20: W
=23: MWh
=26: bar
=29: ft
=32: FPM
=35: ohm
=38: l/s
=41: m
3
/s
=44: kg/m
=47: Pa
=50: gal/m
=53: ft
3
/m
=56: lb/m
=59: ft/s
=62: ft wg
=65: Mrev
=68: m/min
C615 Sleep Mode
Selection
0
0
1
1
When the sleep mode is selected, the inverter
output is switched OFF, if the frequency
reference (or PID output) remains below the
sleep mode enter frequency for the set time
period. Sleep mode can be used with or without
PID control.
=0: Disable
=1: Enable
C616 Sleep Mode Enter
Frequency
Hz
0.10
0.00
600.00
0.01 This is the frequency used to activate the sleep
mode and turn off the inverter.
C617 Sleep Mode Active
Delay
Sec
0
0
999
1
The inverter output will be turned off if the
frequency reference (or PID output) remains
below sleep mode enter frequency.
C618
Sleep Mode Wake
Up Band
%
5.0
0.0
100.0
0.1
This is set with respect to the max frequency
and used as hysteresis when leaving the sleep
mode. The inverter will be turned on when the
frequency reference (or PID output) exceeds the
sleep mode enter fre wake up band.
C619
Sleep Mode Leave
Condition
1
1
2
1
Define the condition to leave the sleep mode.
=1: Freq Ref > C616 Sleep Mode Enter Freq
=2: Freq Ref > A102 Min Freq
Содержание Axpert-Eazy AMT-011-4
Страница 2: ...Amtech ii...
Страница 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Страница 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Страница 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Страница 38: ...Amtech 4 10 4 This page is intentionally left blank...
Страница 46: ...Amtech 5 8 5 This page is intentionally left blank...
Страница 216: ...Amtech 13 6 13 This page is intentionally left blank...
Страница 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Страница 239: ...Notes...
Страница 240: ...Notes...
Страница 241: ......
Страница 242: ...AMTECH...