For a four-quadrant power supply system, the components include the
Model 430 Programmer, the four-quadrant 4Q06125PS power supply,
and associated interconnection cabling. The diagram on page 29
illustrates the interconnects for the AMI Model 4Q06125PS-430 Power
Supply system.
Referring to the diagram on page 29, ensure the cabling is connected in
the following manner:
CAUTION
For multi-axis systems
3
, ensure the power supply and
magnet load cables are connected only to the equipment
associated with the axis (Z-axis, Y-axis, or X-axis) for which
the cable is labeled.
a. Connect the power supply
OUTPUT
terminal
ì
to the positive
magnet current lead
î
.
NOTE
The use of locking hardware is recommended for all high-current
connections.
CAUTION
Do not overtighten the hardware on the interconnection
terminals (refer to specifications table on page 8 for torque
limits). Overtightening can result in damage to the
terminals.
b. Connect the negative magnet current lead
ï
to the positive (+)
resistive shunt terminal
ñ
on the back of the Model 430
Programmer.
c. Connect the negative (
−
) resistive shunt terminal
ó
on the back of
the Model 430 Programmer to the power supply
COMMON
terminal
r
.
d. Connect the DB15 cable from the
PROGRAM OUT
connector
~ä
on the back of the Model 430 Programmer to the
ANALOG I/O
connector
s
on the rear of the power supply.
e. Install an instrumentation cable between the magnet support stand
top plate connector
t
and one of the
MAGNET STATION
connectors
~å
on the rear of the Model 430 Programmer.
f. Optional: Install an instrumentation cable between one of the
LHe
LEVEL / TEMP
~ã
connectors on the rear of the Model 430
3. Refer to page 37.
Содержание 430
Страница 2: ......
Страница 16: ...XVI REV 9 AMERICAN MAGNETICS INC FOREWORD SAFETY SUMMARY ...
Страница 28: ...12 REV 9 AMERICAN MAGNETICS INC INTRODUCTION OPERATING CHARACTERISTICS ...
Страница 64: ...48 REV 9 AMERICAN MAGNETICS INC INSTALLATION POWER UP AND TEST PROCEDURE ...
Страница 208: ...192 REV 9 AMERICAN MAGNETICS INC SERVICE RETURN AUTHORIZATION ...
Страница 248: ...232 REV 9 AMERICAN MAGNETICS INC APPENDIX SHORT SAMPLE MODE ...