Status LED’s (continued)
Ethernet Status LED’s
Link Status –
On when there is a physical link
between the Ethernet port of the Networked
Driver and the Ethernet port of the device the
driver is plugged into. This LED will flash
when data is being transmitted over the Ether-
net link.
Module Status (MS) LED –
The Module Status
LED is a bi-color red/green LED. The state of
the LED depends on the state of the network
adapter module.
Table R1.3 Module Status LED States
Network Status (NS) LED –
The Network Status LED is a bi-color red/green LED. The state of the LED
depends on the protocol the SMD34E2 is configured to.
Table R1.4 Network Status LED States
LED State
EtherNet/IP Definition
Modbus TCP Definition
PROFINET Definition
Off
No Power
No Power
No power
Alternating
Red/Green
Power up Self-Test
Power up Self-Test
Power up Self-Test
Flashing
Green
Waiting for valid
physical connection to the
network.
Waiting for valid
physical connection to the
network.
Not Implemented
Steady Green
Drive and Network are
operational.
Drive and Network are
operational.
Device Name or IP Address
are set.
Flashing Red
Network Connection
Timeout
Not Implemented
Device Name or IP Address
are not set.
Steady Red
Major Fault. Cycle power
to the unit to attempt to
clear the fault.
Major Fault. Cycle power
to the unit to attempt to
clear the fault.
Major Fault. Cycle power to
the unit to attempt to clear the
fault.
LED State
EtherNet/IP Definition
Modbus TCP Definition
PROFINET Definition
Off
No Power OR
No IP Address
No Power OR
No IP Address
No power, duplicate IP address
on the network, or no connec-
tion to IO Controller.
Alternating
Red/Green
Power up Self-Test
Power up Self-Test
Power up Self-Test
Flashing
Green
Ethernet connection,
but no CIP
connections
Indicates number of connec-
tions with 2 second delay
between groups. The unit
supports up to 5 concurrent
connections.
On-line, Stop state. A connec-
tion with the IO Controller is
established and it is in its
STOP state.
Steady Green
Valid Ethernet
network and CIP con-
nections
Not Implemented
On-line, Run state. A connec-
tion with the IO Controller is
established and it is in its RUN
state.
Flashing Red
Network Connection
Timeout
Not Implemented
Not Implemented
Steady Red
Duplicate IP address on network.
Not Implemented
1
MS
NS
2
Figure R1.2 Ethernet Status LED’s
Содержание SD17060E2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S172 E2 Technology E2 Technology...
Страница 10: ...ABOUT THIS MANUAL Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 10 Notes...
Страница 22: ...UL CUL RECOGNIZED INSTALLATIONS Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 22 Notes...
Страница 54: ...CALCULATING MOVE PROFILES Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 54 Notes...
Страница 88: ...COMMAND MODE DATA FORMAT Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 88 Notes...
Страница 106: ...INSTALLING AN AMCI NETWORKED DRIVER Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 106 Notes...
Страница 130: ...ETHERNET IP EXPLICIT MESSAGING Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 130 Notes...
Страница 134: ...MODBUS TCP CONFIGURATION Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 134 Notes...
Страница 144: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...