20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254 Fax: (860) 584-1973 http://www.amci.com
Networked Indexer/Driver User Manual
G
ENERAL
I
NSTALLATION
G
UIDELINES
93
System Layout Considerations (continued)
Minimize Voltages in the System Enclosure
You will want to minimize the voltage in the enclosure that houses your control system to minimize EMI and
voltage transients. In many cases, three phase is used to power the machine's motors and the control system is
powered by one of the phases. Ideally, the three phase power, it's disconnect, fuses, filtering, and all three
phase controls such as motor starters, are housed in their own enclosure. The single phase used to power the
control system is then brought into a separate enclosure built exclusively for the control system.
Power Supply Sizing
A properly sized power supply is vital to system operation. The best guideline that we can give you is to buy
the best supply your budget allows and consider the surge requirements of the components you are attaching
to the supply.
Component Placement
Once you have established the proper categories of all of the system's wires and cables and determined all of
your components you can determine proper component placement and conductor routing within the system
enclosure.
The following guidelines are for noise immunity only. Follow all local codes for safety
requirements.
There are three general guidelines to follow when placing components:
Keep as much physical space between the classes of conductors as possible.
Minimize the distance that conductors run in parallel with each other to minimize capacitive coupling.
If conductors must cross, they should do so at right angles to minimize inductive coupling.
If you have a PLC in your system, be sure to consider the spacing of the modules within the rack. Do not
place an AC output module next to low level DC input module unless absolutely necessary. For example,
consider placing low level input modules on the left side of the rack, high power AC output modules on the
right side, and medium power I/O in the center. This should help you maximize the spacing of I/O wiring
within the enclosure.
Содержание SD17060E2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S172 E2 Technology E2 Technology...
Страница 10: ...ABOUT THIS MANUAL Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 10 Notes...
Страница 22: ...UL CUL RECOGNIZED INSTALLATIONS Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 22 Notes...
Страница 54: ...CALCULATING MOVE PROFILES Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 54 Notes...
Страница 88: ...COMMAND MODE DATA FORMAT Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 88 Notes...
Страница 106: ...INSTALLING AN AMCI NETWORKED DRIVER Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 106 Notes...
Страница 130: ...ETHERNET IP EXPLICIT MESSAGING Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 130 Notes...
Страница 134: ...MODBUS TCP CONFIGURATION Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 134 Notes...
Страница 144: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...