20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254 Fax: (860) 584-1973 http://www.amci.com
21
REFERENCE 2
UL/
C
UL R
ECOGNIZED
I
NSTALLATIONS
UL Required Information
If your installation is to meet UL requirements, you must be aware of the following information when using
the SD17060E2 or SD31045E2.
Maximum surrounding air temperature is +50°C
The driver does not incorporate internal motor overload protection.
The driver does not provide motor over temperature protection.
The driver does not provide overspeed protection.
The driver shall be used in pollution degree 1 or 2 environments. If the driver is mounted in an enclo-
sure, this enclosure must meet these requirements.
All wiring to the driver shall be R/C (AVLV2), minimum rating of 80°C, 300V, except secondary low-
voltage circuit wiring.
Use 75°C copper conductors only.
Terminals shall be tighten to manufacturer’s recommended torques
Power Connector shall be rated for a minimum 12A, 600V, in a pollution degree 2 environment
†
Motor Connector shall be rated for a minimum 16A, 600V, in a pollution degree 2 environment
†
I/O Connector shall be rated for a minimum 8A, 300V, in a pollution degree 2 environment
†
† The mating connectors supplied with these units meet these requirements. Additional mating connectors
can be ordered directly from Phoenix Contact under the following part numbers:
Table R2.1 Mating Connectors
The SD17060E2 and SD31045E2 drivers are Underwriter Laboratory Inc.
®
listed
devices. It is listed as “Industrial Control Equipment” under the control number
60GB. The UL file number is E231137. These units are appropriate for UL and cUL
applications.
Location
Phoenix Contact Part Number
Power
1737822
Motor
1912919
I/O
1803633
Содержание SD17060E2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S172 E2 Technology E2 Technology...
Страница 10: ...ABOUT THIS MANUAL Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 10 Notes...
Страница 22: ...UL CUL RECOGNIZED INSTALLATIONS Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 22 Notes...
Страница 54: ...CALCULATING MOVE PROFILES Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 54 Notes...
Страница 88: ...COMMAND MODE DATA FORMAT Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 88 Notes...
Страница 106: ...INSTALLING AN AMCI NETWORKED DRIVER Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 106 Notes...
Страница 130: ...ETHERNET IP EXPLICIT MESSAGING Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 130 Notes...
Страница 134: ...MODBUS TCP CONFIGURATION Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 134 Notes...
Страница 144: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...