CONTROL UNITS СU-TR230-868 / СU-TR400-868
33
33
MaLfUNCTIONS aNd RECOMMENdaTIONS fOR THEIR ELIMINaTION
MaLfUNCTION
PROBaBLE CaUSE
RECOMMENdaTIONS
With frequent use, the doors
stop during movement;
control commands do
not lead to subsequent
movement of doors.
For drives TR series
(400 V 3 ~) there is an
inscription
E0
(drive with
switches) or
E5
(drive with
encoder)
Motor thermal fuse is
activated
Allow the drive motor to cool
When closing, the doors
stop to move and then open
Safety device is
activated when closing
Remove interference with the movement
of the door leaf
Check the operation of the photocells,
safety edge or other devices (inputs
PH1
and
SE
,
tab.
2, connector 20)
Control unit does not
respond to an obstacle
on the optical axis of the
photocells when closing
Violation of the
operating conditions of
photocells, interaction
with other devices
Make sure that there is no possible
reflection of infrared rays from the
photocells, interaction with other
photocells, direct sunlight on the
photocell receiver
Photocells are defective
Check the efficiency of the photocells;
replace them if necessary
Table 20
UNIT MOdEL
fUSE LOCaTION
fUSE
QUaNTITy
CU-TR230-868
To access, you need to unscrew
the two screws
3
, remove the
connectors and cover
5
(
fig.
8)
Т 6.3 A 250 V AC
Ø5×20
2
CU-TR400-868
To access, you need to unscrew
the two screws
3
, remove the
connectors and cover
5
(
fig.
9).
aTTENTION!
Use fuses filled with
quartz sand
Т 10 A 500 V AC
Ø6.3×32
3
CU-TR230-868 /
CU-TR400-868
To access, unscrew the four screws
6
,
remove the connectors and cover
13
(
fig.
8 / 9)
Т 0.8 A 250 V AC (FU1)
Ø5×20
for CU-TR230-868
Ø6.3×32
for CU-TR400-868
1
Т 1 A 250 V AC (FU2)
Ø5×20
1
Содержание CU-TR230-868
Страница 2: ......
Страница 40: ......
Страница 78: ......
Страница 119: ...117 117 200 310 164 270 R40 90 118 244 271 350 377 2 3 ...
Страница 122: ...120 120 8 14 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 11 12 13 ...
Страница 123: ...121 121 9 14 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 11 12 13 ...
Страница 129: ......