background image

 

 

 

Manual 

WAGO I/O SYSTEM 750 XTR  

 

 

 

750-624/040-00x  

Field Supply Filter 24 VDC HI XTR 

Filter Module for Field-Side Power Supply (Surge); 

24 VDC; Higher Isolation; Extreme 

Version 1.4.0  

 

 

 

Содержание 750-624/040-00 Series

Страница 1: ...Manual WAGO I O SYSTEM 750 XTR 750 624 040 00x Field Supply Filter 24 VDC HI XTR Filter Module for Field Side Power Supply Surge 24 VDC Higher Isolation Extreme Version 1 4 0...

Страница 2: ...8 87 84 45 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always app...

Страница 3: ...ice Precautions 11 3 Device Description 14 3 1 View 16 3 2 Connectors 17 3 2 1 Data Contacts Local Bus 17 3 2 2 Power Jumper Contacts Field Supply 18 3 2 2 1 Variant 750 624 040 000 18 3 2 2 2 Variant...

Страница 4: ...nments 40 6 1 Marking Configuration Examples 41 6 1 1 Marking for Europe According to ATEX and IECEx 41 6 1 2 Marking for the United States of America NEC and Canada CEC 45 6 2 Installation Regulation...

Страница 5: ...erated according to the instructions in this manual in the system description for the WAGO I O SYSTEM 750 XTR and in the manual for the used fieldbus coupler controller Consider power layout of the WA...

Страница 6: ...ry Indicates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if...

Страница 7: ...le 3 Font Conventions Font Type Indicates italic Names of paths and data files are marked in italic type e g C Program Files WAGO Software Menu Menu items are marked in bold letters e g Save A greater...

Страница 8: ...ents All changes to the coupler or controller should always be carried out by qualified personnel with sufficient skills in PLC programming 2 1 3 Use of the 750 Series in Compliance with Underlying Pr...

Страница 9: ...y the user The following actions will result in the exclusion of liability on the part of WAGO Kontakttechnik GmbH Co KG Repairs Changes to the hardware or software that are not described in the opera...

Страница 10: ...of electrical and electronic equipment can be harmful to the environment and human health 2 1 4 1 2 Packaging Packaging contains materials that can be reused PPWD 94 62 EU and 2004 12 EU packaging gui...

Страница 11: ...equate protection against UV irradiation Guarantee mechanical stability Restrict access to authorized personnel and may only be opened with tools Ensure disconnect and overcurrent protection The devic...

Страница 12: ...aterials having seeping and insulating properties The components are not resistant to materials having seeping and insulating properties such as aerosols silicones and triglycerides found in some hand...

Страница 13: ...ces please ensure that environmental factors personnel work space and packaging are properly grounded Use only direct current DC for insulation testing Both the system voltage and field voltage side a...

Страница 14: ...ia certification under the standards of leading agencies such as Germanischer Lloyd and Lloyd s Register Proper certified operation is ensured by using these filter modules This also applies to XTR I...

Страница 15: ...e the field voltage Mixed operation Mixed operation standard XTR modules within a node is possible when groups of modules are electrically isolated on the field side i e electrically isolated power su...

Страница 16: ...s not have any power jumper contacts designed as blade contacts on the left side Table 4 Legend for Figure View Pos Description Details See Section 1 Marking possibility with Mini WSB 2 Status LEDs De...

Страница 17: ...s which are available as self cleaning gold spring contacts Figure 2 Data Contacts Do not place the I O modules on the gold spring contacts Do not place the I O modules on the gold spring contacts in...

Страница 18: ...ia power contacts The maximum current that can flow through the power jumper contacts is 10 A The power jumper contacts can be damaged and the permissible operating temperature can be exceeded by high...

Страница 19: ...r 24 VDC HI XTR Manual Version 1 4 0 3 2 2 2 Variant 750 624 040 001 Figure 1 Power Jumper Contacts Table 6 Legend for Figure Power Jumper Contacts Contact Type Function 1 Spring contact Potential fee...

Страница 20: ...DC HI XTR Manual Version 1 4 0 3 2 3 CAGE CLAMP Connectors Figure 4 CAGE CLAMP Connectors Table 7 Legend for Figure CAGE CLAMP Connectors Designation Connector Function 24 V IN 2 Input field supply 24...

Страница 21: ...re 5 Display Elements Table 8 Legend for Figure Display Elements Designation LED State Function Status of operating voltage field supply C Off No 24 V field supply voltage on the power jumper contacts...

Страница 22: ...WAGO I O SYSTEM 750 XTR 750 624 040 00x Field Supply Filter 24 VDC HI XTR Manual Version 1 4 0 3 5 Schematic Diagrams Figure 6 Schematic Diagram Variant 750 624 040 000 Figure 7 Schematic Diagram Var...

Страница 23: ...ply Table 10 Technical Data Supply Voltage supply via CAGE CLAMP connectors under laboratory conditions for ambient operating temperature 40 C 55 C for ambient operating temperature 55 C 70 C 24 VDC p...

Страница 24: ...echanical Conditions Table 14 Technical Data Mechanical Conditions Vibration resistance Max 5g Follow the installation instructions 3 6 5 Climatic Environmental Conditions Table 15 Technical Data Clim...

Страница 25: ...O I O SYSTEM 750 which you can find via the internet under www wago com DOWNLOADS Documentation System Description The following approvals were granted for the 750 624 040 00x I O module Conformity ma...

Страница 26: ...TR 750 624 040 00x Field Supply Filter 24 VDC HI XTR Manual Version 1 4 0 The following shipbuilding approvals are pending for the 750 624 040 00x I O module ABS American Bureau of Shipping DNV GL LR...

Страница 27: ...I electrical equipment Equipment requirements in the types of protection EN 60079 7 Electrical equipment in e type of protection with ec level of protection EN 60079 15 Electrical equipment in the n t...

Страница 28: ...1000 shocks per axis and direction half sine EN 50155 EN 61373 Random vibration Category 1 classes A and B Shock 5g 30 ms Category 1 classes A and B Environmental Requirements EN 61850 3 Achieved EN...

Страница 29: ...e Surge EN 61000 4 5 EN 60255 26 1 kV conductor conductor 2 kV conductor ground Conducted Disturbances Induced by High frequency Fields EN 61000 4 6 EN 60255 26 10 V 150 kHz 80 MHz Magnetic Fields Wit...

Страница 30: ...15 Damped Oscillatory Waves EN 61000 4 18 EN 60255 26 IEEE C37 90 1 1 25 kV conductor conductor 2 5 kV conductor ground Voltage Dips Short term Interruptions and Voltage Fluctuations to DC Supply Inpu...

Страница 31: ...GHz 6 GHz 60 dB V m AV 3 GHz 6 GHz Shipbuilding Class B 80 dB V m 50 dB V m QP 150 kHz 300 kHz 50 dB V m 34 dB V m QP 0 3 MHz 30 MHz 54 dB V m QP 30 MHz 2 GHz 24 dB V m QP 156 MHz 165 MHz Shipbuilding...

Страница 32: ...for EMC A or EMC B Table 20 Standards and Rated Conditions for Rail Applications EN 50155 Class Standard Compliance 4 1 Rated Operating Conditions 4 1 1 Altitude above sea level AX EN 50125 1 4 1 2 A...

Страница 33: ...acts are sharp edged Handle the I O module carefully to prevent injury Do not touch the blade contacts Insert I O modules only from the proper direction All I O modules feature grooves for power jumpe...

Страница 34: ...work when devices are energized High voltage can cause electric shock or burns Switch off all power to the device prior to performing any installation repair or maintenance work Temperature range app...

Страница 35: ...O module snapped in place the electrical connections for the data contacts and power jumper contacts if any to the fieldbus coupler controller or to the previous or possibly subsequent I O module are...

Страница 36: ...ed to each CAGE CLAMP Do not connect more than one conductor at one single connection If more than one conductor must be routed to one connection these must be connected in an up circuit wiring assemb...

Страница 37: ...VDC HI XTR Manual Version 1 4 0 5 2 Power Supply Concept The following figure shows the power supply concept of a fieldbus node of the WAGO I O SYSTEM 750 XTR for standard compliant use in shipping s...

Страница 38: ...40 000 7 Supply module 230 V AC DC extreme 750 612 040 000 8 XTR end module 750 600 040 000 Potential groups UF1 Field supply 1 24 VDC US System supply 24 VDC UF2 Field supply 2 24 VDC UF3 Field suppl...

Страница 39: ...figuration buffering is not implemented internally To achieve power outages of 1 ms to 10 ms according to IEC61131 2 determine the buffering appropriate for your node configuration and structure it as...

Страница 40: ...2 hazardous areas and shall be used in accordance with the marking and installation regulations The following sections include both the general identification of components devices and the installati...

Страница 41: ...00x Field Supply Filter 24 VDC HI XTR Manual Version 1 4 0 6 1 Marking Configuration Examples 6 1 1 Marking for Europe According to ATEX and IECEx Figure 13 Marking Example According to ATEX and IECE...

Страница 42: ...IIC Explosion group of dust T135 C Max surface temperature of the enclosure without a dust layer Dc Equipment protection level EPL Mining I Equipment group Mining M2 Category High level of protection...

Страница 43: ...43 750 624 040 00x Field Supply Filter 24 VDC HI XTR Manual Version 1 4 0 Figure 15 Marking Example for Approved Ex i I O Module According to ATEX and IECEx Figure 16 Text Detail Marking Example for...

Страница 44: ...a dust layer Dc Equipment protection level EPL Mining I Equipment Group Mining M2 M1 Category High level of protection with electrical circuits which present a very high level of protection Ex Explosi...

Страница 45: ...d States of America NEC and Canada CEC Figure 17 Marking Example According to NEC Figure 18 Text Detail Marking Example According to NEC 500 Table 24 Description of Marking Example According to NEC 50...

Страница 46: ...pment protection level EPL Associated apparatus with intrinsic safety circuits for use in Zone 20 IIC Group T4 Temperature class Gc Equipment protection level EPL Figure 20 Text Detail Marking Example...

Страница 47: ...mark nA Type of protection ia IIIC Type of protection and equipment protection level EPL Associated apparatus with intrinsic safety circuits for use in Zone 20 IIC Group T4 Temperature class Gc Equip...

Страница 48: ...nting when replacing components The product is an open system As such the product must only be installed in appropriate enclosures or electrical operation rooms to which the following applies Can only...

Страница 49: ...e in particular Operating DIP switches coding switches or potentiometers Replacing fuses Wiring connecting or disconnecting of non intrinsically safe circuits is only permitted in the following cases...

Страница 50: ...telephone networks or telecommunication cables WARNING The radio receiver module 750 642 may only be used to connect to external antenna 758 910 WARNING Product components with fuses must not be fitt...

Страница 51: ...uctor to a CAGE CLAMP 36 Figure 12 Power Supply Concept 37 Figure 13 Marking Example According to ATEX and IECEx 41 Figure 14 Text Detail Marking Example According to ATEX and IECEx 41 Figure 15 Marki...

Страница 52: ...onmental Conditions 24 Table 16 Standards and Rated Conditions for Explosion Protection Applications 27 Table 17 Climatic and Mechanical Environmental Conditions and Shipbuilding 28 Table 18 EMC Immun...

Страница 53: ...WAGO I O SYSTEM 750 XTR 53 750 624 040 00x Field Supply Filter 24 VDC HI XTR Manual Version 1 4 0...

Страница 54: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 571 887 0 Fax 49 571 887 844169 E Mail info wago com Internet www wago com...

Отзывы: