BOSS – Installation, Operation and Maintenance Manual
A l e n c o n S y s t e m s L L C - P a g e
|
34
Reset Command –
This command puts the BOSS in startup allowing it to pre-
charge the capacitors connected on the output.
**Note:
The BOSS will not pre-charge or startup without
providing the above two parameters.
After pre-charging the capacitors to the desired output
voltage, the DCDC’s transition to RUN, adjusting the frequency to obtain the desired current set
point. As the frequency goes down the current drawn begins to rise. This continues until
frequency limits are approached.
**NOTE:
Frequency Range - BOSS: 60 ≤ f (KHz) ≤ 160
Figure 31: Alencon’s HMI – The HUB
** NOTE:
Do not change direction of power flow if your DC source cannot act as a load. If
this is the case you will have to manually swap input and output cables
Figure 30: Reset Command