BOSS – Installation, Operation and Maintenance Manual
A l e n c o n S y s t e m s L L C - P a g e
|
36
Verify the BOSS DCDC’s communicate via the HUB
o
Check all 4 DCDC’s and their GUID’s show up
o
Clear any or all existing faults using the clear command
Figure 34: HUB display of the 4 DCDC's
Apply Input Voltage from the DC Source
Set the voltage level on the variable voltage DC load.
o
Hit Reset command – wait for BOSS to transition to standby
o
Establish Power Flow Direction i.e. BUS
BAT (when DC Source connected to the
BUS terminals)
o
Provide Current Set Point
Observe the current flowing at a specified set point.
Make small changes to the voltage on the source to simulate DC Bus voltage
fluctuations. Observe the current of the BOSS and confirm that it follows the set
point.
Make small changes to the voltage on the load to simulate battery charge and
discharge behavior. Observe the current of the BOSS and confirm that it follows
the set point.