Specification and Manual 

 

 

Customer :     

                 

 

 

Description :             

Heat Exchanger 70 W/K

 

Customer Part No. :                                                                                          Rev.:   
Delta Model No. :           

HEX070PB

                                                            Rev :    02 

Sample Date Code:   
Sample Issue Date :      Jun.03.2020 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
DELTA ELECTRONICS, INC. 
252, SHANGYING ROAD, GUISHAN INDUSTRIAL ZONE, 

TEL : 886-(0)3-3591968 

TAOYUAN CITY 33341, TAIWAN 

  FAX : 886-(0)3-3591991 

 

 

Please send one copy of this specification back after 
you signed approval for production pre-arrangement   

Approved by : 

Date : 

 

Summary of Contents for HEX070PB

Page 1: ...0PB Rev 02 Sample Date Code Sample Issue Date Jun 03 2020 DELTA ELECTRONICS INC 252 SHANGYING ROAD GUISHAN INDUSTRIAL ZONE TEL 886 0 3 3591968 TAOYUAN CITY 33341 TAIWAN FAX 886 0 3 3591991 Please send one copy of this specification back after you signed approval for production pre arrangement Approved by Date ...

Page 2: ...ise Rated Current 3 8A 4 6A 鄭誌雲 01 22 20 鄭誌雲 01 22 20 涂雅森 01 22 20 陳加偉 01 22 20 02 Remove section 7 陳俊堯 06 03 20 陳俊堯 06 03 20 涂雅森 06 03 20 莊德財 06 03 20 ISSUE DATE SAMPLE HISTORY DRAWN APPROVED DESCRIPTION REV CUSTOMER CUSTOMER P N DELTA MODEL HEX070PB CHECKED PAGE 1 OF 1 History 000 ...

Page 3: ...Cutout 3 1 6 Configuration Maintenance 4 1 7 Thermal and Airflow 5 2 Electrical specification 6 2 1 Indicator Connector HEX panel side 6 2 2 Standalone control mode 7 3 Environmental Condition 8 3 1 Operating Temperature 8 3 2 Storage Temperature 8 3 3 Operation Humidity 8 3 4 Ingress Protection Rating 8 4 Reliability Table 8 5 Safety Certification 8 6 Installation Notice 9 7 Reclaim 9 ...

Page 4: ...ng HEX unit and be sure to install it correctly After completing the installation make sure that the unit operates properly during the start up operation Meaning of WARNING and CAUTION notices Warning Failure to follow these instructions properly may result in personal injure or loss life Caution Failure to observe these instructions properly may result in property damage or personal injury which ...

Page 5: ...or trained users in shops in light industry and on farms or for commercial use by lay persons Caution 1 Install the HEX on a wall door strong enough to withstand the weight of the unit 2 Do not allow a child to mount on the outdoor unit or avoid placing any object on it 3 Do not block air inlets or exits 4 Do not install the HEX at any place where there is a danger or flammable gas leakage 5 To av...

Page 6: ...IV Specification for Approval Customer Description Heat Exchanger 70 W K Customer P N Rev Delta model no HEX070PB Rev 02 Sample revision Date Code Sample issue date Quantity INTERNAL EXTERNAL ...

Page 7: ...orms to IP55 protection rating 1 2 Main Feature Model Number Dimensions Weight Mounting method Dimension H x W x D without flange mm 940 x 490 x 100 Application N A Outdoor Weight Kg 17 5 ref Mounting Method N A Door Side Environmental Protection Performance Operating Temperature Range C 10 to 65 ice free Protection for Dust Wind and Water External IEC 60529 IP55 Noise 1 5m dB A 65 Operational Dat...

Page 8: ...Part no Delta model no HEX070PB Page 2 1 3 Dimension 1 Material Case SPCC sheet t 1 0mm 2 Finish Power paint 75um min Color RAL7035 3 2 Dimensional Tolerance 1 0mm 0 04 ...

Page 9: ...Part no Delta model no HEX070PB Page 3 1 4 Mounting Panel Cutout TOLERANCE 1MM ...

Page 10: ...mulation Please do not use strong water jet to impact the center of fan and the surface of condenser The bottom hole of the heat exchangers is used for drainage please clear drain holes when the maintenance Please also notice that following 1 Check wires are connected correctly and the insulation is not cracking or broken 2 Do not wipe the product with organic solvent volatile substances like tolu...

Page 11: ...low won t be mixed since the waste heat can be dissipated from the cabinet to the ambience Internal temperature sensor is placed at return air stream to provide reliable temperature measurement and safety of operation While on the opposite side cooler air from the out environment will be drawn from the external air inlet side and bring the heat of the HEX out from the external air exhaust side ...

Page 12: ...put Normal open Normal close Connection Pin 3 Pin 4 Pin 5 Pin 4 Control board NTC and fan are in normal status OPEN CLOSE Power off or control board is disabled CLOSE OPEN NTC resistance is over range such as open circuit or short circuit CLOSE OPEN Fan speed is lower than 50 of definition or fan locked CLOSE OPEN LED indicator Fan NTC sensor Normal GREEN GREEN Abnormal or failed RED Blinking RED ...

Page 13: ...Part no Delta model no HEX070PB Page 7 2 2 Standalone control mode HEX can detect temperature inside of cabinet to control cooling capacity Full speed 3150 RPM 10 Half speed 1450RPM 200RPM ...

Page 14: ...l air loop 0 95 RH non condensing 3 4 Ingress Protection Rating IP55 IEC60529 on external side 4 Reliability Table 5 Safety Certification Test item Condition High temperature IEC 60068 2 2 Low temperature IEC 60068 2 1 High temp High humidity IEC 60068 2 14 test Nb Temperature cycle IEC 60068 2 3 Vibration ETSI 300 019 1 4 CLASS 4 1 Ingress protection external side IEC 60529 IP55 GR487 Package bum...

Page 15: ...stacles to make sure the product get enough space for air circulate 7 Reclaim At the end of the unit working life the produce must not be disposed of as urban waste It must be taken to a special local authority differentiated waste collection center or to a dealer providing this service ...