8 – TROUBLESHOOTING
SECTION 8 – TROUBLESHOOTING
Personnel should be familiar with the operation of the VELTRON DPT-
plus
(see Section 5) before performing any
troubleshooting.
Note: Prior to performing any troubleshooting, turn power OFF. After 10 seconds, turn power switch ON. If problem
still exists, proceed with troubleshooting steps.
Problem
No Display and "CPU
Activated"
•
is not blinking.
No output or incorrect output
(Output 1 or 2) and display
responding correctly with
process change.
No output or incorrect output
(Output 1 or 2) and display
not responding or correctly
with process change.
AUTO-zero Function
is not working.
is continuously lit.
is flashing rapidly.
Alarms not working.
Process Signal is Unreliable
is displayed on Line 1 of
display.
Unreliable is displayed on
Line selected to display
Temperature.
Solution
– Verify input power is present at the correct voltage as listed on label and connected to
Terminals 15 and 16.
– Check fuse F1 (see Figure 4.4 for location).
– Review Factory Set-Up Information Sheet for type of output (isolated or non-isolated).
– Check terminal strip wiring for proper installation.
– Perform Transmitter Output Calibration (see Section 6).
– Verify pressure signal lines are connected correctly.
– Verify AUTO-zero valve switch is in the OFF position.
– Check for leaky or obstructed lines between
VELTRON DPT-
plus
and process sensor.
– Check for kinked internal signal pressure lines in transmitter base.
– Verify AUTO-zero is ON and interval is properly set (see Section 5.9).
– Verify AUTO-zero valve switch is in the OFF position.
– Zero value measured during AUTO-zero cycle is between 90 and 100% of span. Transmitter
Input Calibration should be performed as soon as possible (see Section 6.3).
– Zero value measured during AUTO-zero cycle is greater than 100% of span. Transmitter
Input Calibration should be performed immediately (see Section 6.3).
– Verify that Alarm is ON and setpoints are set to correct value (see Section 5.11).
– Check for proper terminal strip wiring and connections (see Section 4.5).
– Verify pressure signal lines are connected correctly (see Section 4.4).
– Verify process is operating within design parameters specified on Factory Set-Up Sheet.
– Verify temperature signal is connected properly according to the type of temperature device
(see Section 4.5).
– Verify temperature signal from temperature device is a 4.0-20.0mADC type.
– Verify temperature device is operating correctly.
If after following the Troubleshooting steps the VELTRON DPT-
plus
continues to operate
improperly, contact the Service Department for further assistance (see Section 10).