5.7 – TRANSMITTER SCALING & CONFIGURATION (con't)
1. While in Main Menu, use or to scroll to:
Transmitter Scaling
and Configuration
2. Press to enter Transmitter Scaling & Configuration menu. Display will indicate: Process
Configuration
3. Press to enter the Process Configuration sub-menu. Display will indicate: Density Comp. Off On
Selection
4. Press and display will indicate current setting of Density Compensation (OFF or ON).
5. Use or to change setting. Once desired setting is displayed, press , new setting will be stored in
memory and display will return to Process Configuration sub-menu as in Step 3.
Note: If user desires not to change the setting and return to the Process Configuration sub-menu, press .
Unit will remain programmed as it was originally.
6. Use or to select remaining parameters to be changed within the Process Configuration sub-menu.
See the following Units Lists for the available Process Units selections for the appropriate Process Type.
See the following Format List for the available Process Format selections.
7. Follow Step 5 to make any changes to parameters.
8. To return to the Transmitter Scaling & Configuration menu, select EXIT in the Process Configuration sub-menu
and press .
Note:
If Process Minimum is selected to be a value greater than zero (0), Output 1 and 2 (if Transmitter is selected
as output) will not increase until the actual process exceeds this selected value. This is known as "Zero
Suppression".
Zero Suppression (Process Minimum ) can be set up to 60% of the Process Maximum selected.
Display of process is not affected by this selection, and will indicate the actual process value.
21