5.14 – ANALOG OUTPUT CONFIGURATION
SECTION 5 – OPERATION
User can select which process variable Output 2 represents.
Process variables available for output are:
– Transmitter Differential Pressure
– Transmitter Flow
– Temperature (only if temperature is a parameter used in Density Compensation)
42
1. While in Main Menu, use or to scroll to:
Analog Output
Configuration
2. Press to enter Analog Output Configuration menu. Display will indicate:
Output 2
Selection
3. Press and display will indicate current setting of Analog Output #2 (NO OUTPUT, TRANSMITTER,
TRANSMITTER D.P., TEMPERATURE).
4. Use or to change setting. Once desired setting is displayed, press . New setting will be stored in
memory and display will return to Analog Output Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to Analog Output Configuration menu, press . Unit
will remain programmed as it was originally.
5. To return to Main Menu, select Return to MAIN MENU in Analog Output Configuration menu and press .
X
- Display Configuration
Analog Output Config.
- Transducer Span Selection
- Output 2 Selection
- Return to MAIN MENU
Output 2
NO OUTPUT
NO OUTPUT
TRANSMITTER
TRANSMITTER D.P.1
TEMPERATURE 2
User Setup Main Menu
Analog Output Config.
Return to
MAIN MENU
Default selection shown.
Available selections:
1 Not available if Process
Type is Diff. Pres.
2 Available only if Density
Compensation is ON or
Temperature is ON.