SECTION 4 – INSTALLATION
4.5 – POWER/SIGNAL CONNECTIONS (con't)
OUTPUT 1
. This output represents the measured process and is provided as either internally powered/non-isolated or
externally powered/isolated. Review the Factory Information Set-Up Sheet (at the end of this manual) to determine how
your unit is configured. Which of the following connection methods to use is determined by how the unit is configured.
INTERNALLY POWER/NON-ISOLATED (Terminals 2(SIG COM) and 3(OUT-1))
. This 4-20mA output is sourced
(powered) by the VELTRON DPT-
plus
. Maximum load resistance is dependent on the power supply voltage, see
load graph (Figure 4.5).
Figure 4.5
EXTERNALLY POWERED/ISOLATED (Terminals 3(OUT-1) and 5 (ISO PWR INPUT))
. Power for this 4-20mA
output is via an external (customer provided) 12-32VDC supply. Maximum load resistance is dependent on the
power supply voltage, see load graph (Figure 4.6)
Figure 4.6