SECTION 5 – OPERATION
30
5.8 – LOW PASS FILTER
User can select level of filtering applied to the transducer output*. Levels are 0 to 8, with 0 representing no filtering and
8 representing maximum filtering.
* This filtering affects all subsequent outputs, displays, alarms, etc., that utilize the transducer output.
1. While in Main Menu, use or , to scroll to:
Low Pass Filter
Selection
2. Press and display indicates current setting of Low Pass Filter; 0 (none) to 8 (Maximum).
3. Use or to change setting. Once desired setting is displayed, press , new setting will be stored in
memory and display will return to Main Menu.
Note: If user desires not to change the setting and return to Main Menu, press . Unit will remain
programmed as it was originally.
X
-
Trans. Scaling & Config.
Low Pass Filter Selection
- Auto-Zero Configuration
Low Pass Filter
1 (Minimum)
0 (none) to
8 (Maximum)
Default selection shown.
Available selections:
User Setup Main Menu