VELTRON DPT-
plus
Air Monitor Corporation
116-010-91.P65 (09/18/09)
VELTRON DPT-
plus
- IO&M Manual
SECTION 5 – OPERATION
5.7 – TRANSMITTER SCALING & CONFIGURATION (con't)
20
- EXIT User Setup
Trans. Scaling & Config.
- Low Pass Filter Selection
User Setup Main Menu
- Process Configuration
- Temperature Configuration
- Calc for Max Diff Pres or Flow
1
- Return to MAIN MENU
Density Comp.
Off/On Selection
Default selection shown.
Available selections:
MASS or
VOLUMETRIC
Exits to Trans.
Scaling &
Configuration Menu
Density Comp Off/On
ON
Density Comp.
Type Selection
2
Density Comp. Type
MASS
ON or OFF
Square Root
Off/On Selection
3
Square Root Off / On
ON
EXIT
Process Configuration
Transmitter Flow
or Transmitter
Velocity
Process Type
Selection
4
Process Type
TRANSMITTER FLOW
See UNITS list for
available selections
Process Units
Selection
Process Units
FLOW SCFM
2 Available only if Density
Compensation is ON.
ON or OFF
See FORMAT list for
available selections
Process Format
Selection
Process Format
FLOW XX,XXX SCFM
Depends on process
Type and Format
Process Minimum
Selection
Process Minimum
FLOW 0 SCFM
Depends on process
Type and Format
Process Maximum
Selection
Process Maximum
FLOW 10,000 SCFM
Sq. Feet; Sq Inches;
Sq Meters; or
Sq. Centimeters
Duct Area Units
Selection
5
Duct Area Units
Square Feet
0.0000
to
3250.0 Sq. Ft.
Duct Area
Selection
5
Duct Area
10.00 Sq Ft
°F, °C, °R or °K
Temperature Units
Selection
Temperature Units
°F
in.Hg, psia, kPa,
mbars or mm WC
BarometrcPresUnits
Selection
Barometrc Pres Units
in.Hg
0% to 100.00%
in 0.01 increments
Output Lockdown
Selection
4
Output Lockdown
10.00 % FS Output
1 Available only if Square Root is ON in
Process Configuration.
3 Available only if Density
Compensation is OFF.
4 Not available only if Square
Root is OFF. If Square Root
is OFF, Process Type is
Differential Pressure (D.P.).
5 Available only if Process
Type is Transmitter Flow.
Available units depends
on Process Type selected.
Trans. Scaling & Configuration
Duct Area Range
000.00 - 325.00 Sq Ft
0.0000 - 3.2500
0.000 - 32.500
0.00 - 325.00
0.0 - 3250.0
Duct Area Range
Selection
5